4 Rockwell Automation Publication 750-IN011F-EN-P - June 2017
PowerFlex 750-Series Power Jumpers
Jumper Installation, Removal, and Storage
Jumper screws (Frames 2…5), wires (Frames 1, 6 & 7), or plugs (Frames 8…10) are used to complete an electrical
connection when installed/connected. When power jumper screws are not used, they are stored on the left interior
chassis wall as shown.
When installing a jumper screw or wire, note the recommended torque listed.
Drive Identification
The ‘Voltage Code’ and ‘Default Power Jumper Configuration’ are on the drive nameplate. Use this information to
perform the proper procedure in the following tables.
ATTENTION: Hazard of equipment damage exists if jumpers are not properly disconnected.
For Frames 2…5, completely remove the jumper screw from the circuit board.
Frames 1, 6 & 7, secure the disconnected jumper wire to the standoff provided.
Frames 8…10 drive assemblies, secure the disconnected jumper plug in the socket that is provided and verify that all drive assemblies are identically configured.
Recommended Torque Values
Frames Recommended Torque Recommended Screwdriver/Socket
1 Not Applicable Not Applicable
2…5 1.36 N•m (12.0 lb•in) 0.14 N•m (1.2 lb•in) 6.4 mm (0.25 in.) flat or T15 Hexalobular
6…7 1.36 N•m (12.0 lb•in) 7 mm socket or T20 Hexalobular
Drive Power Jumpers
Frame 4 Shown
Jumper Screws
Installed
Jumper Screws Not
Installed
Jumper Screw Storage
Cat No. 20G11 N D 011 AA0NNNNN
UL Type 1 - only with Debris Hood and Conduit Plate
UL Open Type/IP20 - without Debris Hood and Conduit Plate
Specifications and Custom Catalog Number
representing options installed at factory.
See Nameplate 2 (Located behind HIM)
for equivalent base catalog number and separate options
Nameplate 1:
Mfd. in 2009 on Jan. 19
Series: A
Input: 3 Phase, 47-63Hz
AC Voltage Range
Amps ND (HD)
Power ND (HD)
Output: 3 Phase, 0-400 Hz
AC Voltage Range
Base Frequency (default)
Continuous Amps ND (HD)
60Sec Ovld Amps ND (HD)
3 Sec Ovld Amps ND (HD)
0-400
50 Hz
342-440 432-528
0-460
60 Hz
xxx
xxx
xxx
xxx
xxx
xxx
xxx
xxx
xxx
xxx
xxx
xxx
xxx xxx xxx xxx
5.5 HP (4 HP) 7.5 HP (5 HP)
N223
Serial Number: xxxxxxxx
Original Firmware: x.xxx
TUV
Rheinland
Product Safety
..
Production inspected
W
E
C
EN 61800-5-1
Made in the U.S.A. Fac1C
400V Class 480V Class
II (2) G D
Functional Safety
Type approved
Voltage Code
Default Power Jumper Configuration