POINT I/O 2 and 4 Relay Output Modules 21
Publication 1734-IN055H-EN-E - August 2016
Specifications
General Specifications
Attribute Value
Outputs per module 1734-OW2 – 2 Form A isolated (normally open) electromechanical relays
1734-OW4 – 4 Form A isolated (normally open) electromechanical relays
Off-state leakage current, max 1.2 mA @ 240V AC, and bleed resistor through snubber circuit
Terminal base screw torque Determined by the installed terminal block.
Power consumption 0.8 W
Power dissipation, max 0.5 W
Backplane power 5V DC, 80 mA
Contact rating
(1)
(1)
Surge Suppression – Connecting surge suppressors across your external inductive load will extend the life of the
module. For additional details, refer to Industrial Automation Wiring and Grounding Guidelines, Allen-Bradley
publication 1770-4.1.
120/240V AC, 2.0 A @ 50/60 Hz
1800 VA make, 180 VA break
(3)
5…30V DC, 2.0 A, R150
(3)
For maximum rating at voltages between the maximum design value and 120V, the maximum make and break ratings
are to be obtained by dividing the volt-amperes rating by the application voltage. For voltages below 120V, the
maximum make current is to be the same as for 120V, and the maximum break current is to be obtained by dividing the
break volt-amperes by the application voltage, but these currents are not to exceed 2 A.
Isolation voltage 250V, tested @ 2550V DC for 60 s, field-side to system, and between
contact sets
Switching frequency, max 1 operation/3 s (0.3 Hz @ rated load)
Expected life of
electrical contacts, min
100,000 operations @ rated load
Enclosure type rating None (open-style)
Wire size 0.25…2.5 mm
2
(22…14 AWG) solid or stranded copper wire rated at
85 ° C (185 ° F), or greater, 1.2 mm (3/64 in.) insulation max
Wiring category
(2)
(2)
Use this conductor category information for planning conductor routing as described in Industrial Automation Wiring
and Grounding Guidelines, publication 1770-4.1.
1 – on signal ports
Pilot duty rating R150
North American temp code T4A
IEC temp code T4