EasyManuals Logo
Home>Allen-Bradley>Control Unit>ProcessLogix B Series

Allen-Bradley ProcessLogix B Series User Manual

Allen-Bradley ProcessLogix B Series
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #26 background imageLoading...
Page #26 background image
26 ProcessLogix and ControlLogix System Redundancy Module
Publication
1757-IN092E-EN-P - November 2007
Chassis State Status Indicator
The Chassis State status indicator identifies whether or not the chassis is
primary.
1757-SRM Module Fault Codes and Display Messages
The 1757-SRM module faults fall into four categories.
Status Conditions
Off No power has been applied to the 1757-SRM module.
The 1757-SRM chassis state is in secondary or failed state.
Green < 1 second Powerup with partner 1757-SRM module determining primary state.
Solid green 1757-SRM chassis state is in a primary state.
Fault Type Description
Minor Recoverable The fault does not stop redundancy operations and
provides you with a recovery mechanism.
The 1757-SRM module may clear some minor
recoverable faults on its own.
Minor Nonrecoverable The fault does not stop redundancy operations.
No recovery mechanism is available.
Major Recoverable The fault will impact redundancy operations, although the
effect may not be immediate.
For example, if the fault occurred in the secondary 1757-SRM
module, it may not affect control until the primary 1757-SRM
module fails.
Major Nonrecoverable The fault is a critical fault. Redundancy operations will
cease.
A switchover may occur.
No recover mechanism is available.
The module may need to be replaced.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley ProcessLogix B Series and is the answer not in the manual?

Allen-Bradley ProcessLogix B Series Specifications

General IconGeneral
BrandAllen-Bradley
ModelProcessLogix B Series
CategoryControl Unit
LanguageEnglish

Related product manuals