64 Rockwell Automation Publication PFLEX-AP005B-EN-P - May 2019
Chapter 2 Analog Speed Follower and Preset Speed
Table 39 - PowerFlex 700 to PowerFlex 750-Series Drive (with optional I/O module)
Shaded table cells indicate factory-set default settings. Please verify
these settings if the drive is not new or a ‘set to factory defaults’ was
never performed.
PowerFlex 700 Drive Parameters PowerFlex 750-Series Drive Parameters
(2)
No. Name Value No. Name Value
41 Motor NP Volts 460 25 Motor NP Volts 460
42 Motor NP Amps 1.6 26 Motor NP Amps 1.6
43 Motor NP Hertz 60 27 Motor NP Hertz 60
44 Motor NP rpm 1785 28 Motor NP rpm 1785
45 Motor NP Power 1 30 Motor NP Power 1
Mtr NP Power Mtr NP Pwr
46 Motor NP Power Units 0-Hp 29 Units 0-Hp
53 Motor Cntl Sel 0-Sensrls Vect 35 Motor Ctrl Mode 1-Induction SV
79 Speed Units 0-Hz 300 Speed Units 0-Hz
81 Minimum Speed 0.0 522
(3)
Min Fwd Speed 0.0
523
(3)
Min Rev Speed 0.0
82 Maximum Speed 60.0 520
(3)
Max Fwd Speed Motor NP Hz/rpm x 1
521
(3)
Max Rev Speed Motor NP Hz/rpm x -1
90
(1)
Speed Ref A Sel Analog In 2 545
(1)
Spd Ref A Sel Port 0 Ref
93
(1)
Speed Ref B Sel Preset Speed 1 550
(1)
Spd Ref B Sel Speed Ref B Stpt
91
(1)
Speed Ref A Hi Max Speed (P82) 547
(1)
Spd Ref A AnlgHi Max Fwd Spd (P520)
92
(1)
Speed Ref A Lo 0.0 548
(1)
Spd Ref A AnlgLo 0.0
101 Preset Speed 1 5 Hz/150 rpm 571 Preset Speed 1 1/12 x (P27 or P28)
102 Preset Speed 2 10 Hz/300 rpm 572 Preset Speed 2 1/6 x (P27 or P28)
103 Preset Speed 3 20 Hz/600 rpm 573 Preset Speed 3 1/3 x (P27 or P28)
104 Preset Speed 4 30 Hz/900 rpm 574 Preset Speed 4 1/2 x (P27 or P28)
105 Preset Speed 5 40 Hz/1200 rpm 575 Preset Speed 5 2/3 x (P27 or P28)
106 Preset Speed 6 50 Hz/1500 rpm 576 Preset Speed 6 5/6 x (P27 or P28)
107 Preset Speed 7 60 Hz/1800 rpm 577 Preset Speed 7 (P27 or P28)
140 Accel Time 1 10.0 535 Accel Time 1 10.0
141 Decel Time 1 10.0 537 Decel Time 1 10.0
322 Analog In 1 Hi 10.0 261 Anlg In0 Hi 10.0
323 Analog In 1 Lo 0.0 262 Anlg In0 Lo 0.0
361 Digital Input 1 8-Run Forward 164 DI Run Forward Port 0 (P220) Input 1
362 Digital Input 2 9-Run Reverse 165 DI Run Reverse Port 0 (P220) Input 2
364 Digital Input 4 15-Speed Sel 1 173 DI Speed Sel 0 Port 0 (P220) Input 3
365 Digital Input 5 16-Speed Sel 2 174 DI Speed Sel 1 Port 0 (P220) Input 4
366 Digital Input 6 17-Speed Sel 3 175 DI Speed Sel 2 Port 0 (P220) Input 5
(1) These default selections will vary between PowerFlex drive models and applications. Set these parameters to your specific application needs.
(2) The optional I/O module is installed in slot 4.
(3) The PowerFlex 750-Series drive offers parameters for speed direction (forward and reverse) that are not available in the PowerFlex 700 series.
‘P’ in all parentheses is an abbreviation for Parameter.
For best possible settings, perform an auto-tune (Rotate Tune) on the
connected motor to pair the motor to the drive.