Aode Machinery Co., Ltd Page 22 of 26
奥德机械有限公司 2012
第八章 异常情况及处理表
Chapter Eight Abnormal Situation and Solution
故障现象
Phenomena
原因
Causes
处理方法
Solutions
1、无法开机
Fail to start up.
1、控制电路开关未打开
Fail to open the controlling circuit
switch
1、将微型断路器开关打开
Open the micro breaker switch
2、欠相。
Default phase.
2、检查电源线。
Check the power wire.
3、高压断电保护
High voltage power off
protection
3、打开机器侧封板,按下压力开关红色复位键
即可
Open the machine side boards, press the red
reset button of pressure switch
2、缺水警报
Water shortage alarm.
1、未开冷却水或压力不够
The cooling water is not opened
or the pressure is not enough.
1、打开冷却水阀门并检查压力情况。
Open the cooling water valve and check the
pressure.
2、冷却水进出口接反
The position of the cooling water
inlet and outlet is not right
2、调换冷却水进出口
Exchange the position of the cooling water
inlet and outlet
3、冷却水或补水口过滤器堵塞
Cooling water or filling water port
blocked
3、清洗过滤器
Clean up the filter
3、泵过载警报
Pump overload
alarming.
1、系统负载过重
System overload.
1、 05A,10A 检查热水出入口阀门是否开启,并
按复归键。
Check if the hot water inlet/outlet valve is
open and press the reset key.
2、 检查泵的电机是否卡死
Check if the motor of pump is stuck
2、电源电压不正常或欠相
Abnormal power supply or
voltage, or phase deficiency.
1、 使用三相电表测三相电压和电流。
Use three-phase electric meter to measure
three phase voltage and electricity.
2、 检查电源端子是否松脱并拧紧,并按复归
键。
Check if the power supply terminal is
loosened, if yes, please screw it and press the
reset key.
3、 电机轴承卡死
Motor bearing stuck
3、更换轴承
Replace the bearing
4、温度偏高、无法降温
Temperature is too high
to fall down
1、电磁阀堵塞。
Solenoid valve blocked.
1、清除电磁阀内水孔杂物并清洗。
Clear up the sundries of water hole in solenoid
valve.
2、电磁阀线圈老化损坏。
Loop of solenoid valve aging and
damaged.
2、请来电我司。
Please call us.
3、冷却水出水被压太大
The pressure of cooling water is
too big
3、冷却水出口直接排空或检查冷却水进出口是
否接反
Cooling water emptying directly or check the
position of the cooling water inlet and outlet