29
FIG. 3.11
FIG. 3.12
Soft light adjustment
11
The soft light can be adjusted betw
een the maximum power
(shown on the display as “00”, i.e. 100%) and the minimum
po
wer (shown on the display as “01”, i.e. 1%). The boiler is
factory set to a value which is suitable for the ignition with any
type of gas (appro
x. 33%).
The value set expressed as a percentage, can be displayed and
adjusted as indicated in Section 3.6.1 (parameter 1)
Maximun Heating Power adjustment
22
The maximum heating power can be adjusted to between the
maximum power allowed by the boiler (24kW) and the minimum
power (8kW). The value is factory set to 70% of the maximum
power.
The value set (expressed as a percentage) canbe displayed and
modified as illustrated in Section 3.6.1 (parameter 2).
The display shows the value between 100% ("00" on the display)
and 1% ("01") of this inter
val.
Ignition Delay adjustment
33
The ignition delay can be adjusted to between 0 and 7
minutes. The delay is factory set to 2 minutes.
The v
alue set can be displayed and modified as illustrated in
Section 3.6.1 (parameter 3)
Maximun Central Heating temperature
44
This parameter allows the setting of the maximum temperature for
the central heating circuit. The value is factory set at 82°C and
can be adjusted as illustr
ated in Section 3.6.1 (par
ameter 4).
Minimum Central Heating temperature
55
This parameter allows the setting of the minimum temperature for
the central heating circuit. The value is factory set at 42°C and
can be adjusted as illustrated in Section 3.6.1 (parameter 5).
FIG.
3.13
FIG. 3.14
FIG.
3.15