1004935-US-1.0 Issue 2008-11-13 9
5.3.3 Multi Voltage Input (MVI)
MVI impulse accepts a dry (no voltage) contact or 6-24 V AC/DC.
Status of lock (operation mode) can be selected through a function selector FS2
which depends on input TB2:11 and 13.
* +6-24 V DC must be connected to TB2:13.
Program selector must not be connected to TB2:13 if input is 6-24 V. Instead, con-
nect program selector to EXB.
MVI impulse will unlock the lock and open the door or only unlock the lock
(changes the operation mode of the operator), when using the function selector FS3.
MVI hold open time can be adjusted between 0 to 30 sec.
FS-2 = OFF (factory setting)
FS-3 = OFF (factory setting)
TB2:11 and 13 TB2:11 and 13
TB2:11 and 13
6-24 V AC/DC*
CSDB (No PS)
OFF
AUTO
EXB OFF OFF
EXB EXIT EXIT
EXB AUTO AUTO
EXB OPEN OPEN
FS-2 = ON
FS-3 = OFF (factory setting)
TB2:11 and 13 TB2:11 and 13
TB2:11 and 13
6-24 V AC/DC*
CSDB (No PS) AUTO
OFF
EXB OFF OFF
EXB EXIT EXIT
EXB AUTO AUTO
EXB OPEN OPEN
FS-2 = OFF (factory setting)
FS-3 = ON
TB2:11 and 13 TB2:11 and 13
TB2:11 and 13
6-24 V AC/DC*
CSDB (No PS) OFF Open door
EXB OFF OFF Open door
EXB EXIT EXIT Open door
EXB AUTO AUTO Open door
EXB OPEN OPEN Open door
FS-2 = ON
FS-3 = ON
TB2:11 and 13 TB2:11 and 13
TB2:11 and 13
6-24 V AC/DC*
CSDB (No PS) Open door OFF
EXB OFF Open door OFF
EXB EXIT Open door EXIT
EXB AUTO Open door AUTO
EXB OPEN Open door OPEN