The new service interval is now set.
Freeze protection function (available with Remote Alarm function on FX 6 to FX 12)
Once the digital controller detects a dewpoint temperature below -2°C during more than 2 minutes, (L2
Alarm), it switches off the refrigerant compressor.
Resetting the dryer after a refrigerant compressor stop (available with Remote Alarm function on
FX6 to FX 12)
Press button 7 to reset the alarm.
The dryer restarts when both the following conditions are true:
• The dewpoint temperature is higher than -2°C
• 30 seconds are passed from the refrigerant compressor stop (minimum balancing pressure stop time).
A countdown is available if the reset is made before the minimum stop time.
Silent alarm function (available with Remote Alarm function on FX6 to FX 12)
To snooze the alarm, press button 7.
4.4 Starting
Attention
To ensure optimum operational efficiency, do not use dryer on/off switch repeatedly
within a short time period.
Wait at least 5 minutes to start the dryer again after stopping to allow pressure
equalization.
To keep the compressed air net free of condensate, start the dryer before starting the
compressor and stop the compressor before stopping the dryer.
Procedure
FX 1 up to FX 12
Instruction book
2920 7112 40 23