2.3.3 ZT/ZR30 up to ZT/ZR45 IEC
Compressor Voltage Frequency Supply cables
ZT/ZR30 200/220V 50/60 Hz 70 mm²
ZT/ZR30 230V 50/60 Hz 70 mm²
ZT/ZR30 380V 60 Hz 35 mm²
ZT/ZR30 400V 50 Hz 35 mm²
ZT/ZR30 460V 60 Hz 25 mm²
ZT/ZR30 500V 50 Hz 25 mm²
ZT/ZR30 690V 50 Hz 10 mm²
ZT/ZR37 200/220V 50/60 Hz 95 mm²
ZT/ZR37 230V 50/60 Hz 95 mm²
ZT/ZR37 380V 60 Hz 50 mm²
ZT/ZR37 400V 50 Hz 35 mm²
ZT/ZR37 460V 60 Hz 35 mm²
ZT/ZR37 500V 50 Hz 25 mm²
ZT/ZR37 690V 50 Hz 16 mm²
ZT/ZR45 200/220V 50/60 Hz 120 mm²
ZT/ZR45 230V 50/60 Hz 120 mm²
ZT/ZR45 380V 60 Hz 50 mm²
ZT/ZR45 400V 50 Hz 50 mm²
ZT/ZR45 460V 60 Hz 50 mm²
ZT/ZR45 500V 50 Hz 35 mm²
ZT/ZR45 690V 50 Hz 25 mm²
2.3.4 ZT/ZR30 up to ZT/ZR45 CSA/UL
Compressor Voltage Frequency Supply cables
ZT/ZR30 200V 60 Hz AWG000 or 2xAWG3
ZT/ZR30 230V 60 Hz AWG000 or 2xAWG3
ZT/ZR30 460V 60 Hz AWG3
ZT/ZR30 575V 60 Hz AWG4
ZT/ZR37 200V 60 Hz 2xAWG1
ZT/ZR37 230V 60 Hz 2xAWG1
ZT/ZR37 460V 60 Hz AWG2
ZT/ZR37 575V 60 Hz AWG3
ZT/ZR45 200V 60 Hz 2xAWG0
ZT/ZR45 230V 60 Hz 2xAWG0
ZT/ZR45 460V 60 Hz AWG1
ZT/ZR45 575V 60 Hz AWG2
Remarks
- Local regulations remain applicable if they are stricter than the values proposed below.
- For 50 Hz compressors, the size is valid for cable PVC with insulation 70°C at ambient
temperature of 40°C.
- For 60 Hz compressors, the size is valid for cable with insulation 90°C at ambient temperature
of 40°C.