The drain pipe must have a downward gradient
(
1/50-1/100
)
.
If the drain pipe is installed ups and downs or upward,it will lead to water back flow or
leakage etc.
During pipe connection, do not use too much force to the drain joint of indoor
unit.
The joint is PT1.
There is a drain hole on each side of indoor unit;unused drain pipe must be closed.
Note
The drain pipe must be wrapped heat insulation material, otherwise it will cause
condensation or water
drops.
Heat insulation material: rubber insulation pipe with thickness more than 8mm.