S19 Pro+ Hydro Server Installation
Note: The frequency of S19 Pro+ Hydro server is fixed with the value 505 MHz. Firmware will stop running
when the Temp (PCB) reaches to 75℃ or the water temperature is either greater than 45℃ or lower than
20℃,there will be an error message “Fatal Error: Temperature is too high!” shown on the Bottom of the
Kernel log page.
4. Monitoring Your Server
4.
Monitoring Your Server
To check the operating status of your server (taking S19 Pro+ Hydro 184T as an example):
1.
Click dashboard marked below to check the server status.
2.
Monitor your server according to the descriptions in the following table:
Number of chips detected in the chain.
Real-time Hashrate of each hash board (GH/s).
Temperature of the inlet (°C).
Temperature of the outlet (°C).
One of the following statuses will appear:
● The Green Icon - indicates normal
● The Red Icon- indicates abnormal