9 Electrical and Gas Leak Checks
9.1 Electrical Safety Checks
After installation, confi rm that all electrical wiring is installed in accordance with
local and national codes / regulations, and according to the Installation Manual. All
testing must be performed by a licensed electrician.
Before test run
Check grounding work
Measure grounding resistance by visual detection and with grounding
resistance tester. Grounding resistance must be less than 0.1Ω.
This may not be required for some locations. Refer to local code
requirements.
During test run
Check for electrical leakage
During the Test Run , use an electroprobe and multimeter to perform a
comprehensive electrical leakage test. If electrical leakage is detected,
turn off the unit immediately and call a licensed electrician to find and
resolve the cause of the leakage.
This may not be required for some locations in the US.
WARNING: Risk of electric shock
All wiring must comply with local and national electrical
codes, and must be installed by a licensed electrician.
9.2 Gas Leak Checks
There are two diff erent methods to check for gas leaks.
Soap and Water Method
Using a soft brush, apply soapy water or liquid detergent to all pipe connection
points on the indoor unit and outdoor unit. The presence of bubbles indicates a
leak.
Leak Detector Method
If using a leak detector, refer to the device’s operation manual for proper usage
instructions.
After confi rming that all pipe connection points DO NOT leak, replace the valve
cover on the outside unit.

Other manuals for Bosch Climate 5000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bosch Climate 5000 Series and is the answer not in the manual?

Bosch Climate 5000 Series Specifications

General IconGeneral
SEER RatingUp to 22
HSPF RatingUp to 10
Wi-Fi ConnectivityYes
Cooling Capacity9000 - 24000 BTU/h
Energy Efficiency Class (Cooling)A+++
Energy Efficiency Class (Heating)A+++
Sound Power Level (Indoor Unit)19 - 45 dB
Sound Power Level (Outdoor Unit)Varies by model, typically 50-60 dB(A)
FeaturesSleep mode, Timer, Self-Cleaning Function
Energy Efficiency Ratio (EER)Varies by model
Coefficient of Performance (COP)Varies by model
Operating Temperature Range (Heating)-15°C - 24°C
Indoor Unit Dimensions (HxWxD)Varies by model
Outdoor Unit Dimensions (HxWxD)Varies by model
Indoor Unit WeightVaries by model
Outdoor Unit WeightVaries by model

Related product manuals