Faults | 75
6 720 810 590 (2015/05)
Greenstar FS
EA No flame detected.
GFA: Safety time expired.
Check that ground lead is properly connected, replace if defective.
Check that gas cock is open.
Check inlet gas pressure; correct if needed.
Check power supply.
Check electrodes for visual damage; replace if defective.
Check flue gas system; clean or repair if defective.
Check gas/air ratio; correct if out of range.
Check gas valve; replace if defective.
In room air operation, check air supply or ventilation apertures.
Clean the condensate trap.
Remove diaphragm at fan inlet connection and check for
contamination or cracks.
Check heat exchanger for soiling ( Chapter 15.1.6, page 68).
Check gas cock; replace if defective.
Insert code plug correctly; replace if defective.
F0 Internal fault Press reset for 3 seconds and release. When the button is released, the
appliance will restart.
Check electrical plug-in contacts and ignition leads; replace PCB if defective.
Check gas/air ratio; correct if out of specification.
F1 Internal data error. Reset boiler to the factory default setting ( service function 8.E).
F7 Flame detected even when burner is off. Check electrodes; replace if defective.
Check flue gas system; clean or repair if defective.
Check PCB for moisture; dry if needed.
FA After switching gas off: Flame is detected. Check gas cock; replace if defective.
Clean condensate trap.
Check electrodes and leads; replace if defective.
Check flue gas system; clean or repair if needed.
Fd Reset button pressed by mistake. Press reset button again.
Check cable harness to safety high limit and gas cock for ground connection.
Temperature gradient limiter: Temperature rise
too fast
Fully open service shut-off valves.
Check electrical connection between heating zone pump and Heatronic.
Check pump plug connection per installation instructions.
Manually test operation of heating zone pump and replace if defective.
Set pump speed correctly to match maximum output.
Display Description Elimination
Table 29 Faults shown on the display

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bosch KWB42-3 and is the answer not in the manual?

Bosch KWB42-3 Specifications

General IconGeneral
BrandBosch
ModelKWB42-3
CategoryBoiler
LanguageEnglish

Related product manuals