EasyManuals Logo

Carrier 16JT Series User Manual

Carrier 16JT Series
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #29 background imageLoading...
Page #29 background image
Actions After Abnormal Shutdown Abnormal
stop occurs automatically when any of the safety devices in
Table 8 sense a condition which might be potentially dam-
aging to the chiller. When this happens the steam valve closes
completely, the alarm buzzer sounds, and the type of prob-
lem is indicated by one of the three fault lights. Also, both
the Stop and Run lights will be on.
The buzzer can be silenced and the circuit reset for restart
by depressing the Stop button, but this should be done only
after noting which fault light is on; or the alarm buzzer stop
button may be depressed to silence the buzzer while the con-
trol circuit remains in a shutdown alarm mode for trouble-
shooting. If the fault is a type which does not allow shut-
down dilution, the condition should be corrected and the chiller
either restarted, or started and stopped for normal
dilution, as quickly as possible to avoid solution crystalli-
zation when the machine cools down.
Actions After Power Interruption If the control
power is interrupted during operation, the chiller stops im-
mediately without the normal shutdown sequence and dilu-
tion. The capacity control valve might be open so the steam
supply valve should be closed immediately.
Solution crystallization can occur if the concentration is
high (e.g., chiller was operating with a relatively large load).
If so, depress the Start button to restart the machine as soon
as possible after the power is restored. The machine will not
restart automatically when power is recovered. If the chiller
cannot be operated because of crystallization, follow the de-
crystallization instructions in the Maintenance Procedures sec-
tion, page 40.
Table 8 —Automatic Stop Safety Devices
CONDITION
CONTROL SAFETY SHUTDOWN SAFETY
SYMBOL RELAY DILUTION INDICATOR
Low chilled water flow (below 50%) 69CW CWX No LD1
Low chilled water temperature (below 36 F [2 C]) 26CW CWX No LD1
Chilled water pump auxiliary contact 88EP CWX No LD1
Cooling water pump auxiliary contact 88CP CWX No LD1
Solution pump motor high temperature 26SP 26MX No LD2
Refrigerant pump motor high temperature 26RP 26MX No LD2
Solution pump motor current overload 51SP 26MX No LD2
Refrigerant pump motor current overload 51RP 26MX No LD2
High-stage generator high pressure (above −.8 in. Hg [−20 mm]) 63GH 63GX Yes LD3
High-stage generator high temperature (above 338 F [170 C]) 26GH 63GX Yes LD3
High absorber pressure (above 400 mm Hg [−15.8 in. Hg]) ABS ABSX No NONE
PERIODIC SCHEDULED MAINTENANCE
Normal preventive maintenance for 16JT absorption chill-
ers requires periodic, scheduled inspection and service. Each
item in the list below is detailed in the Maintenance Proce-
dures section.
Every Day of Operation
1. Log machine and sytem readings.
2. Exhaust purge.
Every Month of Operation
1. Determine absorber loss.
2. Determine noncondensable accumulation rate.
3. Check capacity control adjustment.
Every 2 Months of Operation
1. Check low-temperature cutout.
2. Check Cycle-Guard™ operation.
Every 6 Months of Operation
1. Check refrigerant charge.
2. Check octyl alcohol.
Every Year of Operation
1. Have solution analyzed.
2. Check tubes for scale and fouling.
Every 3 Years of Operation Replace service valve
diaphragms.
Every 5 Years or 20,000 Hours of Operation
(Whichever comes first.)
1. Inspect hermetic pumps.
2. Filter or regenerate the solution if necessary.
MAINTENANCE PROCEDURES
Log Sheets
Readings of machine and system pressure-
temperature conditions should be recorded daily to aid the
operator in recognizing both normal and abnormal machine
conditions. The record also aids in planning a preventive main-
tenance schedule and in diagnosing machine problems.Atypi-
cal log sheet is shown in Fig. 24.
29

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier 16JT Series and is the answer not in the manual?

Carrier 16JT Series Specifications

General IconGeneral
BrandCarrier
Model16JT Series
CategoryChiller
LanguageEnglish

Related product manuals