11
6 - ELECTRICAL DATA FOR UNITS WITH HIGH CONDENSING TEMPERATURES
30HXC 150 and 150A Options
30HXC 080 090 100 110 120 130 140 155 175 190 200 230 260 285 310 345 375
Power circuit
Nominal power supply (Un) V-ph-Hz 400-3-50
Voltage range V 360-440
Control circuit supply The control circuit is supplied via the factory-installed transformer
Max. power input** kW 104 117 131 145 159 174 194 211 230 263 271 310 345 395 422 460 526
Circuit A kW - - - - - -----175195230263211230263
Circuit B kW - - - - - -----96115115132211230263
Max. current drawn (Un - 10%)*** A 190 215 240 265 290 320 355 385 420 480 495 564 630 720 770 840 960
Circuit A A - - - - - -----320355420480385420480
Circuit B A - - - - - -----175210210240385420480
Maximum current drawn (Un)*** A 173 195 218 241 264 291 323 350 382 436 450 514 573 655 700 764 873
Circuit A A - - - - - -----291323382436350382436
Circuit B A - - - - - -----159191191218350382436
Max. starting current, std. unit (Un)**** A 277 312 335 379 402 435 519 546 578 618 1251 1549 1608 1701 1735 1799 1920
Circuit A**** A - - - - - -----1092 1358 1417 1483 1385 1417 1483
Circuit B**** A - - - - - -----9601226 1226 1265 1385 1417 1483
Max. starting current/max. current draw
ratio, unit 1.61 1.60 1.54 1.57 1.52 1.49 1.61 1.56 1.51 1.42 2.78 3.02 2.81 2.60 2.48 2.36 2.20
Max. starting current/max. current draw
ratio, circuit A - - - - - -----3.75 4.21 3.71 3.40 3.96 3.71 3.40
Max. starting current/max. current draw
ratio, circuit B - - - - - ---- 6.03 6.42 6.42 5.80 3.96 3.71 3.40
Max. starting current - reduced current
start (Un)**** A std. std. std. std. std. std. std. std. std. std. N/A N/A N/A N/A N/A N/A N/A
Three-phase short circuit holding current kA 25 25 25 25 25 25 25 25 25 25 N/A N/A N/A N/A N/A N/A N/A
Circuit A kA - - - - - ----.-25252525252525
Circuit B kA - - - - - -----15151515252525
Customer standby capacity, unit or circ. A,
for evaporator water pump connections† kW8 8 81111 111515151515181830303030
** Power input, compressor, at unit operating limits (evaporator water entering/leaving temperature = 15°C/10°C, condenser entering/leaving water temperature = 40°C/45°C) and a nominal
voltage of 400 V (data given on the unit name plate).
*** Maximum unit operating current at maximum unit power input.
**** Maximum instantaneous starting current (maximum operating current of the smallest compressor(s) + locked rotor current or reduced starting current of the largest compressor)
† Current and power inputs not included in the values above
N/A Not available
The 30HXC 080-375 units for high condensing temperatures
are directly derived from the standard models. Their applicat-
ion range is the same as that of the standard units, but permits
operation at condenser leaving water temperatures up to 63°C.
The PRO-DIALOG control offers all the advantages of the
standard units, plus control of the condenser leaving water
temperature.
The main modifications are:
- Use of 30GX compressors
- Modification of electrical components to operate with
compressors for high condensing temperatures.
- Modification of heat exchangers to meet pressure code
requirements (if necessary).
Option 150
These units are designed for traditional applications for water-
cooled units, but for higher condender leaving water
temperatures than 45°C.
Like the standard units they are equipped with condenser
entering and leaving water sensors, installed on the piping.
It is possible to control the machine at the condenser water
outlet, requiring a factory configuration change and the use of
a heating/cooling inlet reversing device.
Option 150A
These units are designed for water-to-water heat pumps.
They are factory configured as heat pumps (heating/cooling
control as a function of the remote reversing device). The
condenser incorporates thermal insulation that is identical to
that of the evaporator.
Technical information
All information is identical to that of the standard 30HXC
units, except for the following paragraphs.
Selection
There are no nominal conditions for this unit type. The
selection is made using the current electronic catalogue.
Dimensions
These are identical to those of the standard 30HXC units. The
only difference is in the diameter of the incoming field wiring
connection, described in the chapter “Recommended selection”.
Refer to the dimensional drawings for these units, before
proceeding with the wiring.
Compressor
See 30GX compressor table.
Options and accessories
All options available for the standard 30HXC units are compa-
tible, except:
Option 5, brine unit Special unit
Option 25, soft start, 30HXC 200-375 units Not available
Attention:
If units have two different operating modes - one with high
condensing temperature and the other with low condensing
temperature - and the transition is made with the unit in
operation, the temperature must not vary by more than 3 K
per minute. In cases where this is not possible, it is recom-
mended to go through a unit start/stop switch (remote start/
stop available for standard units).