EasyManuals Logo

Carrier 30HXC175 User Manual

Carrier 30HXC175
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #25 background imageLoading...
Page #25 background image
25
- Evaporator pump interlock (mandatory)
- Remote on/off switch
- Condenser flow switch (field-supplied, 30HXC only)
- Remote heat/cool switch
- Demand limit external switch 1
- Remote dual set point
- Alarm report by circuit
- Evaporator pump control
- Condenser pump control (30HXC only)
- Remote set point reset or outside air temperature sensor
reset (0-10 V)
IMPORTANT
Before connection of the main power cables (L1 - L2 - L3)
on the terminal block, it is imperative to check the correct
order of the 3 phases before proceeding to the connection on
then terminal block or the main disconnect/isolator switch.
13.1 - Field control wiring
Refer to the Controls IOM and the certified wiring diagram
supplied with the unit for the field control wirting of the following
features:
Recommended wire sections for units with high condensing temperatures (400 V - 3 ph - 50 Hz)
Unit, options 150 + 150A Min. (mm
2
) Wire type L (m) Max. (mm
2
) Wire type L (m)
400 V - 3 ph - 50 Hz by phase by phase
30HXC 080 OPT. 150 1 x 50 XLPE Cu 150 2 x 70 PVC Al 230
30HXC 090 OPT. 150 1 x 70 XLPE Cu 160 2 x 95 PVC Al 260
30HXC 100 OPT. 150 1 x 70 XLPE Cu 160 2 x 95 PVC Al 250
30HXC 110 OPT. 150 1 x 95 XLPE Cu 170 2 x 120 PVC Al 265
30HXC 120 OPT. 150 1 x 120 XLPE Cu 180 2 x 120 XLPE Al 205
30HXC 130 OPT. 150 1 x 120 XLPE Cu 160 2 x 120 XLPE Al 210
30HXC 140 OPT. 150 1 x 150 XLPE Cu 175 2 x 120 XLPE Al 205
30HXC 155 OPT. 150 1 x 185 XLPE Cu 185 2 x 150 XLPE Al 215
30HXC 175 OPT. 150 1 x 240 XLPE Cu 185 2 x 150 XLPE Al 210
30HXC 190 OPT. 150 2 x 95 XLPE Cu 175 2 x 240 XLPE Al 220
30HXC 200 OPT. 150 circ. A 1 x 120 XLPE Cu 170 2 x 150 XLPE Al 270
30HXC 230 OPT. 150 circ. A 1 x 150 XLPE Cu 180 2 x 185 XLPE Al 270
30HXC 260 OPT. 150 circ. A 1 x 185 XLPE Cu 180 2 x 240 XLPE Al 295
30HXC 285 OPT. 150 circ. A 1 x 240 XLPE Cu 170 2 x 185 XLPE Cu 265
30HXC 310 OPT. 150 circ. A 1 x 185 XLPE Cu 180 2 x 240 XLPE Al 300
30HXC 345 OPT. 150 circ. A 1 x 185 XLPE Cu 170 2 x 240 XLPE Al 280
30HXC 375 OPT. 150 circ. A 1 x 240 XLPE Cu 170 2 x 185 XLPE Cu 265
30HXC 200 OPT. 150 circ. B 1 x 35 XLPE Cu 125 2 x 95 PVC Al 320
30HXC 230 OPT. 150 circ. B 1 x 50 XLPE Cu 140 2 x 95 PVC Al 310
30HXC 260 OPT. 150 circ. B 1 x 50 XLPE Cu 140 2 x 95 PVC Al 310
30HXC 285 OPT. 150 circ. B 1 x 70 XLPE Cu 160 2 x 120 PVC Al 325
30HXC 310 OPT. 150 circ. B 1 x 150 XLPE Cu 180 2 x 185 XLPE Al 275
30HXC 345 OPT. 150 circ. B 1 x 185 XLPE Cu 185 2 x 240 XLPE Al 305
30HXC 375 OPT. 150 circ. B 1 x 185 XLPE Cu 160 2 x 240 XLPE Al 280