Page #51 background image
Page 12.4
Adjusting the DeadbandAdjusting the Deadband
MULTI-STAGE OPERATION - Controls up to two Heat and two Cool
stages.
The 2nd Stage of heat or cool is
(A) The 1st Stage has been on for the two minutes.
(B) The temperature spread
than: the setpoint
turned on when:
from the setpoint is equal to or greater
plus the 1st stage deadband (step #19, next
page), plus two degrees.
And
Heat
Setpoint
Cool
Setpoint
Deadband Deadband DeadbandDeadband
db 1 db 1db 2 db 2
(adj. 1-6 )(adj. 0-10 ) (adj. 0-10 )(adj. 1-6 )
1st Stage
turn on
2nd Stage
turn on
1st Stage
turn on
2nd Stage
turn on
Heating
Cooling
TEMPERATURE
DECREASE INCREASE
12