EasyManuals Logo

Carrier 50DP016 User Manual

Carrier 50DP016
16 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #7 background imageLoading...
Page #7 background image
(|")FPT
DRAIN
CONNECTION-l-.
(HALF
COUPLING)
^
r
BASE
RAIL-
LI
TO
TRAP
<J>
Fig.
9
Condensate
Drain
Piping
Details
Step
6
Make
Electrical
Connections
FIELD
POWER
SUPPLY
Unit
is
factory
wired
for
voltage
shown
on
nameplate.
Units
are
provided
with
terminal
block.
When
installing
units,
provide
a
disconnect
per
NEC
of
adequate
size
(Table
2).
All
field
wiring
must
comply
with
National
Electrical
Code
and
local
requirements.
Route
power
lines
through
control
box
end
panel
or
unit
basepan
(Fig.
4)
to
terminal
connections
as
shown
on
unit
wiring
diagram
and
Fig.
10.
i
l
TBl
S
I
[
\d)\
EQUIP
GND
Fig,
10
Field
Power
Wiring
Connections
Operating
voltage
to
compressor
must
be
within
voltage
range
indicated
on
unit
nameplate.
On
3-phase
units,
voltages
between
phases
must
be
balanced
within
2%
and
the
current
must
be
balanced
within
10%.
Use
the
following
formula
to
determine
the
%
voltage
imbalance.
%
Voltage
Imbalance
100
x
max
v
°ltag
e
deviation
from
average
voltage
average
voltage
Example:
Supply
voltage
is
460-3-60.
AB
=
452
volts
BC
=
464
volts
AC
=
455
volts
Average
Voltage
=
452
+
464
+
455
1371
=
457
Determine
maximum
deviation
from
average
voltage:
(AB)
457
452
=
5
volts
(BC)
464
-
457
=
7
volts
(AC)
457
-
455
=
2
volts
Maximum
deviation
is
7
volts.
Determine
%
voltage
imbalance:
7
%
Voltage
Imbalance
=
100
xyjyy
=
1.53%
This
amount
of
phase
imbalance
is
satisfactory
as
it
is
below
the
maximum
allowable
2%.
IMPORTANT:
If
the
supply
voltage
phase
im¬
balance
is
more
than
2%,
contact
your
local
electric
utility
company
immediately.
Unit
failure
as
a
result
of
operation
on
improper
line
voltage
or
excessive
phase
imbalance
constitutes
abuse
and
may
cause
damage
to
electrical
components.
Such
operation
would
invalidate
any
applicable
Carrier
warranty.
FIELD
CONTROL
WIRING
Install
a
Carrier-
approved
accessory
thermostat
assembly
according
to
installation
instructions
included
with
accessory.
Locate
thermostat
assembly
on
a
solid
wall
in
the
conditioned
space
to
sense
average
temperature.
Route
thermostat
cable
or
equivalent
single
leads
of
no.
18
AWG
colored
wire
from
subbase
terminals
through
conduit
in
unit
to
low-voltage
connections
as
shown
on
unit
label
wiring
diagram
and
in
Fig.
11.
NOTE:
For
wire
runs
up
to
50
ft,
use
no.
18
AWG
insu¬
lated
wire
(35
C
minimum).
For
50
to
75
ft,
use
no.
16
AWG
insulated
wire
(35
C
minimum).
For
over
75
ft,
use
no.
14
AWG
insulated
wire
(35
C
minimum).
Set
heat
anticipator
settings
as
indicated
in
Table
3.
Settings
may
be
changed
slightly
to
provide
a
greater
degree
of
comfort
for
a
particular
installation.
Refer
to
accessory
remote
control
panel
instructions
as
required.
THERMOSTAT
ASSEMBLY
REMOVABLE
JUMPER
r~°—\
gfipHS
|wj]
^
[Yi]
@
[G]
[$
L
[
X
]
is
-
ffl
-
is
-
s
irsntr
_
Enfns
iirDi
LOW-VOLTAGE
TERMINAL
BLOCK
IN
UNIT
CONTROL
BOX
Fig.
11
Field
Control
Thermostat
Wiring
Step
7
Make
Outdoor
Air
Inlet
Adjustments
MANUAL
OUTDOOR
AIR
DAMPER
All
units
(except
those
equipped
with
a
factory-installed
econo¬
mizer)
have
a
manual
outdoor
air
damper
to
provide
ventilation
air.
Damper
can
be
preset
to
admit
up
to
25%
outdoor
air
into
return
air
compartment.
To
adjust,
loosen
securing
screws
and
move
damper
to
desired
setting
then
retighten
screws
to
secure
damper
(Fig.
12).
OPTIONAL
ECONOMIZER
Enthalpy
Control
Setting
(location
is
shown
in
Fig.
13)
For
maximum
benefit
of
outside
air,
set
enthalpy
control
to
the
A
setting
(Fig.
14).
7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier 50DP016 and is the answer not in the manual?

Carrier 50DP016 Specifications

General IconGeneral
BrandCarrier
Model50DP016
CategoryFreezer
LanguageEnglish

Related product manuals