56
FAN PERFORMANCE (cont.)
Table 40 – 50TC**14 3 PHASE 12.5 TON HORIZONTAL SUPPLY
CFM
AVAILABLEEXTERNALSTATICPRESSURE(IN.WG)
0.2 0.4 0.6 0.8 1.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
FieldSuppliedDrive
1
Standard Static Option
3438 580 0.82 642 0.99 700 1.16 756 1.34 809 1.53
3750 621 1.03 679 1.21 734 1.40 786 1.59 837 1.79
4063
663 1.28 717 1.47 769 1.67 818 1.88 866 2.09
4375 706 1.56 757 1.77 805 1.98 852 2.20 897 2.43
4688 749 1.89 797 2.11 843 2.34 887 2.57 930 2.81
5000 793 2.26 838 2.50 881 2.74 923 2.98 965 3.23
5313 837 2.69 880 2.93 921 3.19 961 3.44 1000 3.71
5625 882 3.16 922 3.42 961 3.68 999 3.95 1037 4.23
5938 926 3.68 964 3.96 1001 4.23 1038 4.52 --- ---
6250 971 4.26 1007 4.55 --- --- --- --- --- ---
CFM
AVAILABLEEXTERNALSTATICPRESSURE(IN.WG)
1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Medium Static Option
3438 860 1.72 910 1.92 957 2.12 1003 2.32 1048 2.54
3750 885 1.99 932 2.20 978 2.42 1022 2.64 1065 2.86
4063 912 2.31 957 2.53 1001 2.75 1043 2.98 1084 3.22
4375 941 2.66 984 2.89 1026 3.13 1066 3.37
1106
3.62
4688 972 3.05 1013 3.29 1053 3.54 1092 3.80 1130 4.06
5000 1005 3.49 1044 3.74 1082 4.01 1119 4.27 1156 4.55
5313 1038 3.97 1076 4.24 1113 4.52 --- --- --- ---
5625 1073 4.51 --- --- --- --- --- --- --- ---
5938 --- --- --- --- --- --- --- --- --- ---
6250 --- --- --- --- --- --- --- --- --- ---
NOTE: For more information, see General Fan Performance Notes on page 41.
Boldface indicates field---supplied drive is required.
1. Recommend using field ---supplied fan pulley (part no. KR11AK012) and belt (part no. KR29AE055).
2. Recommend using field---supplied fan pulley (part no. KR11AZ002), motor pulley (part no. KR11HY310) and belt (part no.
KR29AF054).
Table 41 – 50TC**14 3 PHASE 12.5 TON VERTICAL SUPPLY
CFM
AVAILABLEEXTERNALSTATICPRESSURE(IN.WG)
0.2 0.4 0.6 0.8 1.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
FieldSuppliedDrive
1
Standard Static Option
3438 616 0.92 679 1.10 735 1.27 786 1.45 835 1.62
3750 661 1.16 719 1.35 773 1.54 822 1.73 869 1.93
4063 706 1.43 761 1.64 812 1.85
860
2.06 904 2.27
4375 752 1.75 804 1.98 852 2.20 898 2.43 941 2.65
4688 798 2.12 847 2.36 894 2.60 937 2.85 979 3.09
5000 844 2.54 891 2.80 936 3.06 978 3.31 1018 3.57
5313 891 3.01 936 3.28 978 3.56 1019 3.83 1057 4.11
5625 938 3.53 981 3.83 1022 4.12 1060 4.41 1097 4.70
5938 986 4.12 1026 4.43 --- --- --- --- --- ---
6250 --- --- --- --- --- --- --- --- --- ---
CFM
AVAILABLEEXTERNALSTATICPRESSURE(IN.WG)
1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Medium Static Option
3438 880 1.80 922 1.98 963 2.15 1002 2.33 1039 2.51
3750 912 2.12 954 2.31 994 2.50 1031 2.70 1068 2.89
4063 947 2.48 987 2.68 1025 2.89 1062 3.10
1098
3.31
4375 982 2.88 1021 3.10 1058 3.32 1094 3.55 1129 3.77
4688 1018 3.33 1056 3.57 1093 3.81 1128 4.04 1162 4.29
5000 1056 3.82 1093 4.08 1128 4.34 1162 4.59 --- ---
5313 1094 4.38 1130 4.65 --- --- --- --- --- ---
5625 --- --- --- --- --- --- --- --- --- ---
5938 --- --- --- --- --- --- --- --- --- ---
6250 --- --- --- --- --- --- --- --- --- ---
NOTE: For more information, see General Fan Performance Notes on page 41.
--- H i g h S t a t i c O p t i o n
Boldface indicates field---supplied drive is required.
1. Recommend using field ---supplied fan pulley (part no. KR11AK012) and belt (part no. KR29AE055).
2. Recommend using field---supplied fan pulley (part no. KR11AZ002), motor pulley (part no. KR11HY310) and belt (part no.
KR29AF054).
50TC