9
Table 4 – MINIMUM -- MAXIMUM AIRFLOWS ELECTRIC HEAT
UNIT
COOLING ELECTRIC HEATERS
Minimum Maximum Minimum Maximum
50TC**04 900 1500 900 1500
50TC**05 1200 2000 1200 2000
50TC**06 1500 2500 1500 2500
50TC**07 1800 3000 1800 3000
50TC**08 2250 3750 2250* 3750
50TC**09 2550 4250 2250* 4250
50TC**12 3000 5000 3000* 5000
50TC**14 3600 6000 3000* 6000
* Minimum electric heat CFM exceptions :
UNIT UNIT VOLTAGE HEATER KW UNIT CONFIGURATION
REQUIRED MINIMUM
CFM
50TC**12
50TC**14
208/230 42.4 Horizontal 3200
50TC**12
50TC**14
208/230 50.0 Horizontal 3200
50TC**12
50TC**14
460 50.0 Horizontal or Vertical 3200
50TC**08
50TC**09
50TC**12
50TC**14
575
17.0
Horizontal or Vertical
2800
34.0 2350
50TC