Wiring inputs and outputs
RTU Open v3 Carrier Proprietary and Confidential CARRIER CORPORATION ©2016
Integration Guide All rights reserved
5
Channel
Number
Type
Signal
Function
Part Number
Wire/Terminal
Numbers
Alternate
Terminals
BO - 5
BO
N/A - Relay
Cool 1 (Y1) Output
N/A
J1
- 8
N/A
BO - 6
BO
N/A - Relay
Humidi-MiZer™
N/A
J11
- 7 & 8
N/A
BO - 7
BO
N/A - Relay
Reversing Valve / High
Speed Fan
N/A
J11
- 5 & 6
N/A
BO - 8
BO
N/A - Relay
Power Exhaust
N/A
J11
- 2 & 3
N/A
- Analog Input
- Analog Output
- Digital Input
- Digital Output
*
Safety Chain Feedback
- 24 Vac required at this wire to provide
Run Enabled
status. Provide a jumper from
J1
- 1 to
J1
- 9 if
no safeties are used. See "To wire inputs and outputs" in the
RTU Open Installation Guide for additional information on the RTU
Open wiring harness assembly terminations.
**
Default input function
***
Parallel screw terminal at
J5
(
J5
- 1 =
J2
- 6,
J5
- 3 =
J1
- 10,
J5
- 5 =
J1
- 2) may be used in place of the associated flying leads
at the harness (Part# OPN-RTUHRN). See "To wire inputs and outputs" in the
RTU Open Installation Guide for additional
information.
1
N.C. contact must be used as a primary safety device for approved fire shutdown operation. N.O. contact for monitoring only.
2
If a function other the default is used, do NOT connect wires from J1-x.

Other manuals for Carrier RTU Open v3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier RTU Open v3 and is the answer not in the manual?

Carrier RTU Open v3 Specifications

General IconGeneral
BrandCarrier
ModelRTU Open v3
CategoryController
LanguageEnglish

Related product manuals