Page 58
8. Capacity Correction Factor for Height Difference
8.1 Heat pump models
Model
ID2-XY 35M
Pipe Length (m)
MC2-Y 35M
Cooling 5 10 20 25
Height difference
H (m)
Indoor Upper
than Outdoor
10 0.973 0.948 0.936
5 0.995 0.983 0.958 0.945
0 1.000 0.988 0.963 0.950
Outdoor Upper
than Indoor
-5 1.000 0.988 0.963 0.950
-10 0.988 0.963 0.950
Heating 5 10 20 25
Height
difference
H (m)
Indoor Upper
than Outdoor
10 0.993 0.978 0.970
5 1.000 0.993 0.978 0.970
0 1.000 0.993 0.978 0.970
Outdoor Upper
than Indoor
-5 0.992 0.985 0.970 0.962
-10 0.977 0.962 0.955