Specifications
Page 63
Model
ID2-XY 160M
Pipe Length (m)
MC2-Y 160T
Cooling 5 15 25 35 50 65
Height
difference
H (m)
Indoor Upper
than Outdoor
30 0.866 0.816 0.767
20 0.908 0.875 0.825 0.774
10 0.951 0.917 0.884 0.833 0.782
5 0.995 0.961 0.927 0.893 0.841 0.790
0 1.000 0.966 0.931 0.897 0.846 0.794
Outdoor Upper
than Indoor
-5 1.000 0.966 0.931 0.897 0.846 0.794
-10 0.966 0.931 0.897 0.846 0.794
-20 0.931 0.897 0.846 0.794
-30 0.897 0.846 0.794
Heating 5 15 25 35 50 65
Height
difference
H (m)
Indoor Upper
than Outdoor
30 0.953 0.929 0.905
20 0.968 0.953 0.929 0.905
10 0.984 0.968 0.953 0.929 0.905
5 1.000 0.984 0.968 0.953 0.929 0.905
0 1.000 0.984 0.968 0.953 0.929 0.905
Outdoor Upper
than Indoor
-5 0.992 0.976 0.961 0.945 0.921 0.898
-10 0.968 0.953 0.937 0.914 0.891
-20 0.945 0.930 0.907 0.883
-30 0.922 0.899 0.876