Make sure the room where the unit is
installed meets all the requirements of the
Current Regulations. In particular, this unit
is an “open chamber” type and must only
be installed and operate in permanently
ventilated places. An insufficient supply of
combustion air will compromise normal
operation and the evacuation of fumes.
Also, the fumes forming under these
conditions are extremely harmful to health
if dispersed in the domestic environment.
Otherwise there may be risk of suffocation
and intoxication or explosions and fire..
Therefore the place of installation must be
free of dust, flammable materials or
objects or corrosive gases.
Position the water heater as close as possible
to the hot water taps, near the sink, but
NEVER above a cooktop. It must also
be situated as close as
possible to the flue or
the start of the flue gas
exhaust pipe.
If the unit is installed inside a cabinet
or joined laterally to other elements,
space must be allowed for removing
the casing and performing normal
maintenance activities.
fig. 5 - Minimum distances
2.3 Assembling the heater
Before assembling the
heater, make sure the
water and gas
connections are properly
secured, identified, and
positioned. See the
dimensions and connections
in section 4.2.
• Fix the plugs and hooks on the wall, in a
central position vertical to the
appliance, as shown in
the figure below.
• Mark the position of the bottom screws
• Hang the water heater on the plugs+hooks
and tighten the screws for fixing
the unit to the wall.