Recommended wiring
MRS – Wiring Diagram
LOAD
EMERGENCY STOP
ACCESS LOCK
CONTROL
SIGNALS
REMOTE S/S
DIESEL/GAS ENGINE
RPM
OIL PRESSURE
WATER TEMP
FUEL LEVEL
STARTER
BATTERY
-
+
FUEL SOLENOID
GENERATOR
G
L1
L2
L3
N
Generator C.B.
SPRINKLER
REMOTE OFF
PE
RS-232C
Interface
Modem or PC
CONTROL
SIGNALS
NOT USED
+24 V
BINARY OUTPUTS
GEN C.B.
STARTER
FUEL SOLENOID
PRESTART
ALARM
READY TO LOAD
D+
CHRG
ALTERNATOR
POWER
8 - 36 V DC
RS 232
-
+
D+
BOOT JUMPER
BO3
BO4
BO5
BO6
BO1
(START
)
BO2
(FUEL
)
BINARY
OUTPUTS
ANALOG INPUTS
RPM
COM
AI1 OIL
AI2 TEMP
AI3 FUEL
RPM IN
RPM GND
BINARY INPUTSGEN. CURRENT
0 - 5 A
GENERATOR VOLTAGE
3 x 230 / 400 V
BI1
BI2
BI3
BI4
BI5
BI6
LB 16
N
L1
L2
L3
L3l
L2l
L1l
COM
EXTENSION MODULE
iL-MRS 15
ECU
Hint:
From IL-2.1 it is possible to start Volvo and Scania engines via CAN bus. See Engines started via
CAN bus.
InteliLite – MRS10/11/15/16, SW version 2.2, ©ComAp – November 2004 9
IL-MRS-2.2.pdf

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite MRS15 and is the answer not in the manual?

ComAp InteliLite MRS15 Specifications

General IconGeneral
BrandComAp
ModelInteliLite MRS15
CategoryController
LanguageEnglish

Related product manuals