Operator Interface AMF
GEN-SET CONTROL BUTTONS
POSITION BUTTON DESCRIPTION
1
START button. Works in MAN mode only. Press this button to initiate the
start sequence of the engine.
2
STOP button. Works in MAN mode only. Press this button to initiate the stop
sequence of the gen-set. Repeated pressing or holding the button for more
than 2s will cancel current phase of stop sequence (like ramping the power
down or cooling) and next phase will continue.
3
FAULT RESET button. Use this button to acknowledge alarms and
deactivate the horn output. Inactive alarms will disappear immediately and
status of active alarms will be changed to "confirmed" so they will disappear
as soon as their reasons dismiss.
4
HORN RESET button. Use this button to deactivate the horn output without
acknowledging the alarms.
5
MODE LEFT button. Use this button to change the mode. The button works
only if the main screen with the indicator of currently selected mode is
displayed.
NOTE:
This button will not work if the controller mode is forced by one of binary
inputs Remote OFF, Remote MAN, Remote AUT, Remote TEST.
IL-NT Operator Guide
©ComAp – December 2008 2