EasyManuals Logo

Daikin 2MXS18NMVJUA User Manual

Daikin 2MXS18NMVJUA
282 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #220 background imageLoading...
Page #220 background image
Troubleshooting for Outdoor Unit SiUS121736EA
207 Service Diagnosis
7.20 Output Overcurrent Detection
Error Code L5
Outdoor Unit LED
Display
A j 1 h 2 h 3 i 4 h 5 h
Method of Error
Detection
An output overcurrent is detected by checking the current that flows in the inverter DC section.
Error Decision
Conditions
A position signal error occurs while the compressor is running.
A rotation speed error occurs while the compressor is running.
An output overcurrent signal is fed from the output overcurrent detection circuit to the
microcomputer.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 5 minutes without any other error
Supposed
Causes
Poor installation condition
Closed stop valve
Defective power module
Wrong internal wiring
Abnormal power supply voltage
Defective outdoor unit PCB
Supply voltage out of specification
Defective compressor

Table of Contents

Other manuals for Daikin 2MXS18NMVJUA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin 2MXS18NMVJUA and is the answer not in the manual?

Daikin 2MXS18NMVJUA Specifications

General IconGeneral
BrandDaikin
Model2MXS18NMVJUA
CategoryAir Conditioner
LanguageEnglish

Related product manuals