SiUS121736EA Troubleshooting for RA Indoor Unit
Service Diagnosis 162
5.7 Mismatching of Indoor Unit and Outdoor Unit
Error Code UA
Method of Error
Detection
The supply power is detected for its requirements (pair type is different from multi type) by the
indoor/outdoor transmission signal.
Error Decision
Conditions
The pair type and multi type are interconnected.
Supposed
Causes
Wrong models interconnected
Wrong wiring of connecting wires
Wrong indoor unit PCB or outdoor unit PCB mounted
Defective indoor unit PCB
Defective outdoor unit PCB
Troubleshooting
(R23001)
Caution
NO
YES
YES
NO
Match the compatible models.
OK?
Correct the connection.
Check the part numbers of the
indoor and outdoor unit PCB
with the Parts List.
If not matched, change for the
correct PCB.
Are the
connecting wires connected
properly?
Check the combination of the
indoor and outdoor unit.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin 4MXS-R Series and is the answer not in the manual?

Daikin 4MXS-R Series Specifications

General IconGeneral
BrandDaikin
Model4MXS-R Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals