EasyManuals Logo
Home>Daikin>Air Conditioner>4MXS-R Series

Daikin 4MXS-R Series User Manual

Daikin 4MXS-R Series
282 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #223 background imageLoading...
Page #223 background image
SiUS121736EA Check
Service Diagnosis 210
8.2 Indoor Fan Motor Connector Check
Check No.02 CTXG, FTXR, CTXS, FTXS, FVXS Series
1. Check the connection of connector.
2. Check motor power supply voltage output (pins 4 - 7).
3. Check motor control voltage (pins 4 - 3).
4. Check rotation command voltage output (pins 4 - 2).
5. Check rotation pulse input (pins 4 - 1).
FDMQ Series
1. Turn the power supply OFF.
2. With the fan motor connector disconnected, measure the resistance between each pin, then
make sure that the resistance is more than the value mentioned in the following table.
FFQ Series
1. Check the connection of connector.
2. Check motor power supply voltage output (pins 5 - 8).
3. Check motor control voltage (pins 5 - 4).
4. Check rotation command voltage output (pins 5 - 3).
Measuring points Judgement
White - Blue 1 M or more
Orange - Blue 100 k or more
Brown - Blue 100 or more
Red - Blue 100 k or more
7
6
5
4
3
2
1
S1 or S200
(R14225)
Motor power supply voltage (310 ~ 340 VDC)
Unused
Unused
GND
Motor control voltage (15 VDC)
Rotation command voltage (1~ 5 VDC)
Rotation pulse input
White
Orange
Brown
Blue
Red
FG
Vsp
Vcc
GND
Vdc/Vm
X8A
(R25080)
8
7
6
5
4
3
2
1
X20A
(R24373)
Motor power supply voltage (290 ~ 330 VDC)
Unused
Unused
GND
Motor control voltage (15 VDC)
Rotation command voltage (0 ~ 5 VDC)
Rotation pulse input
Unused

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin 4MXS-R Series and is the answer not in the manual?

Daikin 4MXS-R Series Specifications

General IconGeneral
BrandDaikin
Model4MXS-R Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals