Installation and operation manual
3
FWEC3
Advanced plus electr
onic controller
FC66002765
AVAILABLE CONFIGURATIONS (PARAMETER
P00)
The LCD contr
oller can be con gured in various ways according
to the type of system. Various con gurations can be obtained
through the P00 parameter (see con guration procedure of
controller parameters).
001
System pipes: 2
Valve: NO
Electrical heater: NO
Speeds: 3
Summer/winter switching logic: LOCAL
002
System pipes: 2
Valve: NO
Electrical heater: NO
Speeds: 3
Summer/winter switching logic: REMOTE
003
System pipes: 2
Valve: NO
Electrical heater: NO
Speeds: 3
Summer/winter switching logic: WATER
004
System pipes: 2
Valve: NO
Electrical heater: NO
Speeds: 4
Summer/winter switching logic: LOCAL
005
System pipes: 2
Valve: NO
Electrical heater: NO
Speeds: 4
Summer/winter switching logic: REMOTE
006
System pipes: 2
Valve: NO
Electrical heater: NO
Speeds: 4
Summer/winter switching logic: WATER
007
System pipes: 2
Valve: NO
Electrical heater: YES
Speeds: 3
Summer/winter switching logic: LOCAL
008
System pipes: 2
Valve: NO
Electrical heater: YES
Speeds: 3
Summer/winter switching logic: REMOTE
ACCESS TO PARAMETER CONFIGURATION
PROCEDURE
switch the thermostat off
push the
at the same time
Use keys
to modify the display value up to the
passwor
d value “10”, and press
.
If it is correct, you will have access to the parameters
Use keys
to scr
oll the various parameters (see
“Parameter list” described above)
press
to con
rm the parameter change (the value
will start ashing)
use keys
to change the value
press
to save the new value setting or to
cancel the modi cation
after completing the modi cation of the parameters
concerned press key
to exit the pr
ocedure
N.B.: the parameter con guration phase is of limited
duration. Once a certain time has elapsed (around
2 minutes) the thermostat will switch back into the
Off status and only the saved changes will be re-
tained.
Value of selected
parameter
selected parameter: P. .
selected
parameter
description
selected
parameter
description