Installation and operation manual
2
FWEC3
Advanced plus electr
onic controller
FC66002765
P04 = water
sensor
-0: not available
-1: available
Based on the set value, the sensor alarm and the electrical
heater functions will be controlled
P05 = use con guration DIN 1/2
- 0: DIN1 = - DIN2 = -
- 1: DIN1 = - DIN2 = OnOff
- 2: DIN1 = Sum/Win DIN2 = -
- 3: DIN1 = Eco DIN2 = -
- 4: DIN1 = Sum/Win DIN2 = On/Off
- 5: DIN1 = Eco DIN2 = On/Off
- 6: DIN1 = Sum/Win DIN2 = Eco
P06 = DIN1 logic:
- 0: [open/closed] = [Cooling/Heating] = [-/ECO]
- 1: [open/closed] = [Heating/Cooling] = [ECO/-]
P07 = DIN2 logic:
- 0: [open/closed] = [OFF/ON] = [-/ECO]
- 1: [open/closed] = [On/Off] = [ECO/-]
P08 = Remote humidity sensor
- 0 : not available
- 1 : available
Based on the set value, the associated probe alarm will
be triggered accordingly.
P09 = DOUT1 con guration:
- 0 : not used
- 1 : indicating operation mode
- 2 : indicating unit cooling/heating mode
- 3 : indicating unit cooling mode
- 4 : indicating unit heating mode
- 5 : indicating ON/OFF
- 6 : indicating sensor alarm triggered
- 7 : external dehumidi cation active
- 8 : external humidi cation active
- 9 : indicating high room temperature
- 10 : indicating low room temperature
- 11 : not used
- 12 : indicating low water temperature
(see “Con guration of digital outputs”)
P10 = DOUT1 logic:
- 0 : not used
- 1 : indicating operation mode
(see “Con guration of digital outputs”)
P11 = DOUT2 con guration: same as parameter P09 but
for digital output 2.
(see “Con guration of digital outputs”)
P12 = DOUT2 logic: same as parameter P10 but for digital
output 2.
(see “Con guration of digital outputs”)
P13 = room relative humidity SETPOINT (see “Con guration
of digital outputs)
P14 = AOUT1/2 con guration: con guration of the two
analog outputs 0-10V depending on the type of fan ( non-
modulating or modulating) and the type of valve(s) (ON/
OFF or modulating). For further details see “Con guration
of analog outputs”.
KEY BOARD (SEE FIGURE 3)
On/Of
f key: Thermostat On/Off. During the
procedure of parameter modi cation, it permits to
return to normal operating conditions
Up and Down keys: changing of thermostat set-
ting temperatur
e (Heating: [5.0-30.0°C], Cooling:
[10.0-35.0°C]). During the procedure of parameter
modi cation, they are used to select the parameters
or to change their value
SEL key: in the heating mode, the electric electrical
heater can be selected as auxiliary function
Mode key: selection of Heating/Cooling operating
mode
Fan key: selection of operating speed
EC key: selection of Economy mode
ACTIVE KEY COMBINATIONS
with OFF thermostat: access to circuit board con guration
parameters (password=10)
with thermostat ON: display of current water temperature
(if air sensor is present and correctly con gured through
parameter P04) and hour set on the internal clock
selection of Minimum temperature function
selection of dehumidify option
keypad locking/unlocking (passwor
d=99);
access to time pr
ogramming parameters (password=5)
In any display mode other than the normal one, about 2 mi-
nutes after the last button was pressed the controller will go
back into the standard display mode.
BOARD CONFIGURATION
The boar
d can be con gured according to the type of unit/
system to be governed by changing some parameters.
PARAMETER LIST
P00
= controller configuration (see “Available
con gurations”) to select the type of unit to be managed.
P01 = type of controller installation
-000: on the unit
-001: wall mounted
P02 = Modbus address. In order for the change in this
parameter to become active (excepting in the case of
internal transfer between slave values) it is necessary
to switch the power off and back on again at the end of
programming):
-0: serial communication disabled
-1-247: Slave
-255: Master
P03 = neutral zone [20-50°C/10]; parameter used in case of
con gurations with automatic cooling/heating changeover
according to air temperature.