6 Capacity tables
6 - 3 Capacity Correction Factor
Indoor air
temperature
14.0 °CWB 16.0 °CWB 18.0 °CWB 19.0 °CWB 20.0 °CWB 22.0 °CWB 24.0 °CWB
20.0 °CDB 23.0 °CDB 26.0 °CDB 27.0 °CDB 28.0 °CDB 30.0 °CDB 32.0 °CDB
FXHQ32
TC 0.707 0.692 0.745 0.768 0.788 0.819 0.844
SHF 1.098 1.181 1.127 1.102 1.082 1.055 1.042
FXHQ63
TC 0.695 0.702 0.749 0.772 0.791 0.821 0.844
SHF 1.120 1.169 1.122 1.098 1.079 1.058 1.060
FXHQ100
TC 0.690 0.697 0.757 0.779 0.798 0.829 0.856
SHF 1.123 1.169 1.114 1.091 1.073 1.055 1.057
FXHQ-A
3D079901
Capacity correction factor Te = 9°C