8 | Charging refrigerant
Installer reference guide
45
ARXM50-71+RXM42~71R2V1B + RXP50~71M2V1B + RXA42+50B2V1B +
RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B
R32 split series
4P513661-9J – 2020.05
8 Charging refrigerant
In this chapter
8.1 About charging refrigerant..................................................................................................................................................... 45
8.2 About the refrigerant ............................................................................................................................................................. 46
8.3 Precautions when charging refrigerant ................................................................................................................................. 47
8.4 To determine the additional refrigerant amount .................................................................................................................. 47
8.5 To determine the complete recharge amount ...................................................................................................................... 47
8.6 To charge additional refrigerant ............................................................................................................................................ 47
8.7 To fix the fluorinated greenhouse gases label....................................................................................................................... 48
8.1 About charging refrigerant
The outdoor unit is factory charged with refrigerant, but in some cases the
following might be necessary:
What When
Charging additional refrigerant When the total liquid piping length is
more than specified (see later).
Completely recharging refrigerant Example:
▪ When relocating the system.
▪ After a leak.
Charging additional refrigerant
Before charging additional refrigerant, make sure the outdoor unit's external
refrigerant piping is checked (leak test, vacuum drying).
INFORMATION
Depending on the units and/or the installation conditions, it might be necessary to
connect electrical wiring before you can charge refrigerant.
Typical workflow – Charging additional refrigerant typically consists of the following
stages:
1 Determining if and how much you have to charge additionally.
2 If necessary, charging additional refrigerant.
3 Filling in the fluorinated greenhouse gases label, and fixing it to the inside of
the outdoor unit.
Completely recharging refrigerant
Before completely recharging refrigerant, make sure the following is done:
1 All refrigerant is recovered from the system.
2 The outdoor unit's external refrigerant piping is checked (leak test, vacuum
drying).
3 Vacuum drying on the outdoor unit's internal refrigerant piping is performed.
NOTICE
Before completely recharging, perform vacuum drying on the outdoor unit's internal
refrigerant piping as well.