Pump Down Operation
In order to protect the environment, be sure to pump down when relocating or disposing of the unit.
1) Removethevalvecapfromliquidstopvalveandgasstop
valve.
2) Carryoutforcedcoolingoperation.
3) After5to10minutes,closetheliquidstopvalvewitha
hexagonalwrench.
4) After2to3minutes,closethegasstopvalveandstopforced
coolingoperation.
Forced cooling operation
■
Using the indoor unit ON/OFF switch
PresstheindoorunitON/OFFswitchforatleast5seconds.(Theoperationwillstart.)
• Forcedcoolingoperationwillstopautomaticallyafteraround15minutes.
Tostoptheoperation,presstheindoorunitON/OFFswitch.
■
Using the indoor unit’s remote controller
1) Press“MODE”buttonandselectthecoolingmode.
2) Press“ON/OFF”buttontoturnonthesystem.
3) Pressbothof“TEMP”buttonand“MODE”buttonatthesametime.
4) Press“MODE”buttontwice.(
willbedisplayedandtheunitwillenterforcedcoolingoperation.)
• Forcedcoolingoperationwillstopautomaticallyafteraround30minutes.
Tostoptheoperaion,press“ON/OFF”button.
■
Using the outdoor unit forced cooling operation switch
Forcedcoolingoperationcanbeperformedwhentheoutdoorunitforced
coolingoperationswitchispressedwithinaround3minutesafterpower
issupplied.
Pushon“
”(SW1)withascrewdriver.(Theoperationwillstart.)
• Forcedcoolingoperationwillstopautomaticallyafteraround15minutes.
Tostoptheoperation,presstheswitch(SW1).
Wiring
WARNING
•
Donotusetappedwires,strandedwires,extensioncords,orstarburstconnections,astheymaycauseoverheating,electricalshock,orre.
•Donotuselocallypurchasedelectricalpartsinsidetheproduct.(Donotbranchthepowerforthedrainpump,etc.,fromthe
terminalblock.)Doingsomaycauseelectricshockorre.
•Besuretoinstallagroundfaultcircuitinterrupterbreaker.(Onethatcanhandlehigherharmonics.)
(Thisunitusesaninverter,whichmeansthatitmustbeusedagroundfaultcircuitinterrupterbreakercapablehandling
harmonicsinordertopreventmalfunctioningofthegroundfaultcircuitinterrupterbreakeritself.)
•Useanall-poledisconnectiontypebreakerwithatleast1/8inch(3mm)betweenthecontactpointgaps.
•Whencarryingoutwiringconnection,takecarenottopullattheconduit.
•Donotconnectthepowerwiretotheindoorunit.Doingsomaycauseelectricshockorre.
•Donotturnonthesafetybreakeruntilallworkiscompleted.
1)
Striptheinsulationfromthewire(3/4inch(20mm)).
2) Connecttheconnectionwiresbetweenthe
indoorandoutdoorunitssothattheterminal
numbersmatch.Tightentheterminalscrews
securely.Werecommendaathead
screwdriverbeusedtotightenthescrews.
Gas stop valve
Valve cap
Hexagonal wrench
Close
Liquid stop valve
Service port
Push
Screwdriver
Power supply
terminal block
Forced cooling
operation switch
(SW1)
1
2
3
1 2 3
L1L2
GR
Safety
breaker
15A
Ground fault
circuit interrupter
Ground
Use AWG16 if the connection wire
length is less than 32.8ft (10m), or
AWG14 if it is 32.8ft (10m) or more.
Outdoor unit
Indoor
unit
Power supply
60Hz 208-230V
Use AWG 14 wires.