PAGE 21
Installer Setup
This feature allows the thermostat to display temperature in
Fahrenheit or Celsius.
Fahrenheit or Celsius (setup step 56)
Humidity and Dehumidity (Setup Steps 40-44, 75-76)
Humidity Only With Heat (Setup Step 40) - When this step is set to ON,
Humidity will not run without a demand for Heat.
Fan With Humidity Demand (Setup Step 41) - Specifies if the fan should be turned
on with a demand for Humidity. (This step will only appear if step 40 is set to OFF.)
Cool To Dehumidify (Setup Step 43) - Specifies if the cooling equipment is
allowed to turn on exclusively to lower room humidity. (If set to OFF the
following two steps will not appear.)
Max Dehum Overcool (Setup Step 44) - Specifies how many degrees below
the Cool setpoint the air conditioning will run to satisfy a Cool to Dehumidify
demand. (0˚- 5˚)
Humidty Output Polarity (Setup Step 75)
Dehumidify Output Polarity (Setup Step 76)
Humidity Output Normally Open - means no voltage is sent to the HUM
output when there is no demand for humidity.
Humidity Output Normally Closed - means voltage is sent to the HUM
output when there is no demand for humidity.
Dehumidify Output Normally Open - means no voltage is sent to the
DEHUM output when there is no demand to dehumidify.
Dehumidify Output Normally Closed - means voltage is sent to the
DEHUM output when there is no demand to dehumidify.
D_TSTATD2200C-2_Manual_HR.pdf 29 8/29/13 1:11 PM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin TSTATD2200C-2 and is the answer not in the manual?

Daikin TSTATD2200C-2 Specifications

General IconGeneral
BrandDaikin
ModelTSTATD2200C-2
CategoryThermostat
LanguageEnglish

Related product manuals