FXLQ20~63P7VEB
VRV System air conditioners
4PW53089-1B
Installation and operation manual
2
Optional accessories
There are two types of remote controllers: wired and wireless.
Select a remote controller according to customer request and
install in an appropriate place.
Refer to catalogues and technical literature for selecting a
suitable remote controller.
For the following items, take special care during
construction and check after installation is finished
Notes to the installer
Read this manual carefully to ensure correct installation. Be
sure to instruct the customer how to properly operate the system
and show him/her the enclosed operation manual.
Explain to the customer what system is installed on the site. Be
sure to fill out the appropriate installation specifications in the
chapter "What to do before operation" of the outdoor unit
operation manual.
This unit can be installed on the floor or be mounted to a wall.
IMPORTANT INFORMATION REGARDING THE
REFRIGERANT USED
This product contains fluorinated greenhouse gases covered by the
Kyoto Protocol.
Refrigerant type: R410A
GWP
(1)
value: 1975
(1)
GWP = global warming potential
Periodical inspections for refrigerant leaks may be required
depending on European or local legislation. Please contact your local
dealer for more information.
SELECTING INSTALLATION SITE
1 Select an installation site where the following conditions are
fulfilled and that meets your customer's approval.
- Where optimum air distribution can be ensured.
- Where nothing blocks air passage.
- Where condensate water can be properly drained.
- Where the floor or wall is strong enough to bear the indoor
unit weight.
- Where sufficient clearance for maintenance and service can
be ensured.
- Where piping between indoor and outdoor units is possible
within the allowable limit. (Refer to the installation manual of
the outdoor unit.)
- This is a class A product. In a domestic environment this
product may cause radio interference in which case the user
may be required to take adequate measures.
-Keep indoor unit, outdoor unit, power supply wiring and
transmission wiring at least 1 meter away from televisions
and radios. This is to prevent image interference and noise in
those electrical appliances. (Noise may be generated
depending on the conditions under which the electric wave is
generated, even if 1 meter is kept.)
- When installing the wireless remote controller kit, the
distance between wireless remote controller and indoor unit
might be shorter if there are fluorescent lights who are
electrically started in the room. The indoor unit must be
installed as far as possible away from fluorescent lights.
- Do not place objects that are susceptible to moisture directly
beneath the indoor or outdoor units. Under certain
conditions, condensation on the main unit or refrigerant
pipes, air filter dirt or drain blockage may cause dripping,
resulting in fouling or failure of the object concerned.
2
note
(a)
The air outlet direction can be chosen by rotating the discharge grill.
(b)
100 mm in case of wall mounting
unit of measurement = mm
Tick
when
checked
Is the indoor unit fixed firmly?
The unit may drop, vibrate or make noise.
Is the gas leak test finished?
It may result in insufficient cooling or heating.
Is the unit fully insulated and checked for air leaks?
Condensate water may drip.
Does drainage flow smoothly?
Condensate water may drip.
Does the power supply voltage correspond to that shown on the
name plate?
The unit may malfunction or components may burn out.
Are wiring and piping correct?
The unit may malfunction or components may burn out.
Is the unit safely grounded?
Dangerous at electric leakage.
Is the wiring size according to specifications?
The unit may malfunction or components may burn out.
Is nothing blocking the air outlet or inlet of either the indoor or
outdoor units?
It may result in insufficient cooling or heating.
Are refrigerant piping length and additional refrigerant charge
noted down?
The refrigerant charge in the system might not be clear.
NOTE
Make sure no short circuit of air is caused when
placing the unit directly under a windowsill.
100 100
1000
>20
A
B
C
C
A
A Front side
B Air inlet direction
C Air outlet
direction
(a)
1750
B
<1750
C
B
(b)
>20 20
C
AA
B
C
B

Other manuals for Daikin VRV

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin VRV and is the answer not in the manual?

Daikin VRV Specifications

General IconGeneral
BrandDaikin
ModelVRV
CategoryAir Conditioner
LanguageEnglish

Related product manuals