AK-CT 450A User Guide RS8GR602 © Danfoss 2016-10 11
Data communication
The controller has xed built-in MODBUS data communication.
If there is a requirement for a dierent form of data
communication, a Lon RS 485 module can be inserted in the
controller.
The connection must then be to terminal RS 485.
(To use a Lon RS 485 module and gateway type AKA 245
the module must be Version 6.20 or higher.)
It is not possible, however, to show all parameters available
in AK-CT 450A).
Important
All connections to the data communication MODBUS and RS 485
must comply with the requirements for data communication
cables. See literature: RC8AC.
Display
The controller has two plugs for a display. Here display type
EKA 163B or EKA 164B (max. length 15m) can be connected.
EKA 163B is a display for readings.
EKA 164B is both for readings and operation.
(It is not possible to connect a display to the Modbus terminals,
as in the other AK-CC 450 controllers.)
Refrigeration
Heat
Neutral zone
If there are two cooling sections,
the bottom plug will be the A
section and the top plug will be
the B section.
If there is one cooling section,
the displays will be the same for
both plugs.
Override
The controller contains a number of functions which can be used together with the override function in the master gateway/system
manager.
Function via data communication Function in gateway/system manager Used parameters in AK-CT 450A
Start of defrosting Defrost control / Time schedule / Defrost group --- Def start
Coordinated defrost Defrost control / Defrost group --- HoldAfterDef / - - - DefrostState
Prevent defrost start --- Disable Def
Day/Night schedule Day/Night control / Time schedule / Light zone --- Night setback
Light control Day/Night control / Time schedule O39 light Remote
Forced closing Forced Close / Injection ON / AKC ON --- Forced cl.
Forced cooling --- Forced cool
Rail heat link to dew point / Enhanced railheat --- Dew point
P0 optimization P0 Optimization The controller supports P0 optimization
Heating function
The heating function is used to prevent the temperature
becoming too low, e.g. in a cutting room, etc. The limit for
when the heating function cuts o is set as an oset value
under the current cutout limit for the refrigeration thermostat.
This ensures that refrigeration and heating do not occur
simultaneously. The dierence for the heating thermostat has
the same value as for the refrigeration thermostat. To prevent
that the heating thermostat cuts in during short-term drops
in air temperature a time delay can be set for when to change
from refrigeration to heating.