AK-CC550 Manual RS8EN502 © Danfoss 02-2010 13
5
6
7
9
10
8
Thefollowinguseshavesomespecialfunctions
which in brief are:
Application 5
”Two-compressor”operation.
The two compressors must be of the same size.
Onstart-up(afterdefrosting,operationalstop,
etc.)bothcompressorsarestartedwithasettime
shift.Onecompressorstartsathalfthedierential
so that an optimum adaptation of compressor
capacitytakesplaceforthecurrentloadinthe
appliance/room.Thereisautomaticruntime
equalisation between the compressors.
Foramoredetaileddescriptionpleasereferto
earlier sections in the manual.
Application 6
Hotgasdefrosting.
Hotgasdefrostingisadaptedtocommercial
appliances/roomswithlimitedsystemlling.
Onerelaycontrolsthemainvalveinthesuction
line.
Achangeoverrelaycontrolsboththehotgas
valveandthedrainvalve.
This means that there is no time delay between
stops of hot gas and start of draining.
Application 7
Control of night blinds
Night blinds follow the status of the light function
– when the light is switched on, the night blinds
areupandwhenthelightisswitchedo,the
nightblindsaredown.Inadditionadigitalinput
providestheoptionofforcedopeningofthe
blindssothattheappliancecanbelledwith
products.
Application 8
Heatthermostat
The heat thermostat is typically used if the
temperature is to be controlled within narrower
limits, e.g. for cutting rooms, etc. The heating
thermostatcanbesetasadierenceinrelationto
the cutout limit for the refrigeration thermostat so
that simultaneous refrigeration and heating are
avoided.
Application 9
Two refrigeration sections – two defrost outputs
This application is for refrigeration appliances with
onevalve,twoevaporatorsandtworefrigeration
sections. The temperature is controlled and is
alwaysalarmmonitoredaccordingtotheS4
temperature.Forthistheproductsensorisusedas
adefrostingstopsensorforevaporatorno.2.
Application 10
Tworefrigerationsections–individualalarm/
displayviaS3
This application is for refrigeration appliances with
onevalve,oneevaporatorandtworefrigeration
sections. The temperature is always controlled
accordingtotheS4temperature.Theproduct
sensorisusedasanextraS3sensorforsection
no.2.Alarmmonitoringanddisplayreadingstake
placeindividuallyviathe"S3"sensorsineach
refrigeration section.