16 Manual RS8EN502 © Danfoss 02-2010 AK-CC 550
Set point 2
Thethermostat’scutoutvaluewhenthethermostatband2isactivatedviaadigital
input.
r21 Cutout2 temp
Correction of signal from S6
Compensation possibility due to long sensor cable
r59 AdjustS6
Selection of thermostat sensor S4% during night operation with night blinds
Hereyoudenethesensorthethermostatistouseforitscontrolfunction.S3,S4,ora
combinationofthem.Withthesetting0%,onlyS3isused(Sin).With100%,onlyS4.
r61 Ther.S4%Ngt
Heat function
SetthesizeoftheNeutralZoneforchangeoverfromcoolingtoheating
r62 HeatNZ
Time delay on transition from refrigeration phase to heating phase.
(thereisnottimedelayontransitionfromheatingphasetorefrigerationphase).
r63 HeatStartDel
Nightsetbck
(startofnightsignal.0=Day,1=Night)
Forcedcool.
(startofforcedcooling)
Forcedclose
(Forcedstopofcooling)
Alarm Alarm settings
Thecontrollercangivealarmindierentsituations.Whenthereisanalarmallthe
light-emittingdiodes(LED)willashonthecontrollerfrontpanel,andthealarmrelay
will cut in.
Withdatacommunicationtheimpor-
tanceoftheindividualalarmscanbe
dened.Settingiscarriedoutinthe
“Alarmdestinations”menuviaAKM.
Alarm delay (shortalarmdelayonairtemperature)
Iftheupperortheloweralarmlimitvaluesareexceeded,atimerfunctionwillcom-
mence.Thealarmwillnotbecomeactiveuntilthesettimedelayhasbeenpassed.
The time delay is set in minutes.
A03 Alarm delay
Time delay for door alarm
The time delay is set in minutes.
Thefunctionisdenedino02,o37orino84.
A04 DoorOpendel
Time delay for cooling (longalarmdelay)
This time delay is used during start-up, during defrost, immediately after a defrost.
Therewillbechange-overtothenormaltimedelay(A03)whenthetemperaturehas
dropped below the set upper alarm limit.
The time delay is set in minutes.
A12 Pulldowndel
Upper alarm limit
Hereyousetwhenthealarmforhightemperatureistostart.Thelimitvalueissetin
°C(absolutevalue).
Thelimitvaluewillberaisedduringnightoperation.Thevalueisthesameastheone
setfornightsetback,butwillonlyberaisedifthevalueispositive.
A13 HighLimAir
Lower alarm limit
Hereyousetwhenthealarmforlowtemperatureistostart.Thelimitvalueissetin°C
(absolutevalue).
A14 LowLimAir
Upper alarm limit for thermostat 2 (Thermostat band 2)
(Samefunctionasforthermostat1)
A20 HighLim2Air
Lower alarm limit for thermostat 2 (Thermostat band 2)
(Samefunctionasforthermostat1)
A21 LowLim2Air
Upper alarm limit for S6 temperature at thermostat 1 A22 HighLim1S6
Lower alarm limit for S6 temperature at thermostat 1 A23 LowLim1S6
Upper alarm limit for S6 temperature at thermostat 2 (Thermostat band 2) A24 HighLim2S6
Lower alarm limit for S6 temperature at thermostat 2 (Thermostat band 2) A25 LowLim2S6
S6 temperature alarm delay
ThealarmisactivatedifoneoftherelevantalarmlimitsA22,A23,A24orA25is
exceeded. The time delay is set in minutes.
(Alarmswillnotactivatewhenthesettingissettothemaximumvalue.)
A26 Al.DelayS6
Delay of a DI1 alarm
Acut-out/cut-ininputwillresultinalarmwhenthetimedelayhasbeenpassed.The
functionisdenedino02.
A27 AI.DelayDI1
Delay of a DI2 alarm
Acut-out/cut-ininputwillresultinalarmwhenthetimedelayhasbeenpassed.The
functionisdenedino37
A28 AI.DelayDI2
Signal to the alarm thermostat
Hereyouhavetodenetheratiobetweenthesensorswhichthealarmthermostat
hastouse.S3,S4oracombinationofthetwo.
Withsetting0%onlyS3isused.With100%onlyS4isused
A36 AlarmS4%
Time delay on S6 (product sensor) for pull-down(longalarmdelay)
This time delay is used for start-up, during defrosting, immediately after a defrost and
after an appliance clean.
Achangeiscarriedouttostandardtimedelay(A26)whenthetemperaturehas
reached below the set upper alarm limit.
The time delay is set in minutes.
A52 PullDdel.S6
Reset alarm
Ctrl.Error(EKCerror)