18 Manual RS8EN502 © Danfoss 02-2010 AK-CC 550
Drip-off time
Hereyousetthetimethatistoelapsefromadefrostanduntilthecompressoristo
startagain.(Thetimewhenwaterdripsotheevaporator).
d06 DripOtime
Delay of fan start after defrost
Hereyousetthetimethatistoelapsefromcompressorstartafteradefrostanduntil
thefanmaystartagain.(Thetimewhenwateris“tied”totheevaporator).
d07 FanStartDel
Fan start temperature
The fan may also be started a little earlier than mentioned under “Delay of fan start
afterdefrost”,ifthedefrostsensorS5registersalowervaluethantheonesethere.
d08 FanStartTemp
Fan cut in during defrost
Hereyoucansetwhetherfanistooperateduringdefrost.
0:Stopped(Runsduringpumpdown)
1:Running(stoppedduring"fandelay")
2: Running during pump down and defrost. After that stopped
d09 FanDuringDef
Defrost sensor
Hereyoudenethedefrostsensor.
0: None, defrost is based on time
1: S5
2:S4
3:Sx.Forapplication1to8and10defrostingisstoppedwhenbothS5andS6have
reachedthesettemperature.Forapplication9defrostingisstoppedindividu-
allyonthetwosectionsofS5/S5B
d10 DefStopSens.
Pumpdown delay
Setthetimewheretheevaporatorisemptiedofrefrigerantpriortothedefrost.
d16 Pumpdwndel.
Drain delay (only in connection with hotgas)
Setthetimewheretheevaporatorisemptiedofcondensedrefrigerantafterthe
defrost.
d17 Drain del
Defrost on demand – aggregate refrigeration time
Sethereistherefrigerationtimeallowedwithoutdefrosts.Ifthetimeispassed,a
defrost will be started.
Withsetting=0thefunctioniscutout.
d18 MaxTherRunT
Delay on stop of heating in the drip tray
The time applies from the time the defrost stops by time or temperature to the time
the heating element in the drip tray needs to be disconnected.
d20 Drip Tray del
Adaptive defrosting
Anadaptivedefrostingisanextradefrostinadditiontothescheduleddefrosts.Here
theadaptivedefrostissetforwhenitcanstartadefrostiftheneedarises:
0:Never
1:Onlyalarmoniceover
2:Itmayonlystartduringdayoperation
3:Itmaystartbothduringdayandnightoperation
4:Itcanonlystartduringnightoperations
d21 AD mode
Restart of adaptive defrosting
The function starts a defrost and when it is complete, the tuning function restarts so
thattheevaporator’sdatacanberegistered.
MUSTONLYBEACTIVATEDDURINGSTANDARDOPERATION.
d22 AD reset
Ifyouwishtoseethetemperatureatthedefrostsensor,pushthecontroller’slower-
mostbutton.(Maybechangedtoanotherfunctionino92.)
Defrost temp.
Ifyouwishtostartanextradefrost,pushthecontroller’slowermostbuttonforfour
seconds.
Youcanstopanongoingdefrostinthesameway
Def Start
Hereyoucanstartamanualdefrost
HoldAfterDef
ShowsONwhenthecontrolleris
operating with coordinated defrost.
Disable def.
Defrost in progress can be stopped
Defrost State
Status on defrost
1=pumpdown/defrost
Parameter for cooling function
Integration time
Expertsettingforinjectionfunction
Thevalueshouldonlybechangedbyspeciallytrainedsta.
n05 Tn sec
Max. value for the superheat reference n09 MaxSH
Min. value for the superheat reference n10 MinSH
MOP temperature
IfnoMOPfunctionisrequired,selectpos.OFF
n11 MOPtemp
(Avalueof15correspondstoOFF)
Temperatureglide (only when using of S1-temperature sensor)
Ifazeotroperefrigerantisused,avaluefortemperatureglidemustbeset.
n12 Glide