AKD 2800
Control unit
On the front of the frequency converter there
is a control panel.
The control panel is divided into four function groups:
1. Six-digit LED display.
2. Keys for changing parameters and shifting
display function.
3. Indicator lamps.
4. Keys for local operation.
All displays of data are in the form of a six-digit LED
display capable of showing one item of operating
data continuously during normal operation. As a
supplement to the display, there are three indicator
lamps for indication of mains connection (ON),
warning (WARNING) and alarm (ALARM). Most of
the frequency converters parameter Setups can be
changed immediately via the control panel, unless
this function has been programmed as Locked [1]
via parameter 018 Lock for data changes.
Control keys
[QUICK MENU] allows access to the parameters
used for the Quick menu.
The[QUICKMENU]keyisalsousedifachangetoa
parameter value is not to be implemented.
See also [QUICK MENU] + [+].
[CHANGE DATA] is used for changing a setting.
The [CHANGE DATA] key is also used for confirming
a change of parameter settings.
[+] / [-] are used for selecting parameters and
for changing parameter values.
These keys are also used in Display mode for selecting
the display of an operating value.
The [QUICK MENU] + [+] keys must be
pressed at the same time to give access to all
parameters. See Menu mode.
[STOP/RESET] is used for stopping the connected
motor or for resetting the frequency converter after a trip.
Can be selected as Active [1] or Not active [0] via
parameter 014 Local stop/reset.InDisplaymode,the
display will flash if the stop function is activated.
NB!:
If the [STOP/RESET] key is set at Not active
[0] in parameter 014 Local stop/reset,and
thereisnostopcommandviathedigital
inputs or serial communication, the motor can
only be stopped by disconnecting the mains
voltage to the frequency converter.
[START] is used for starting the frequency converter.
It is always active, but the [START] key cannot
override a stop command.
Manual initialisation
Disconnect mains voltage. Hold the [QUICK
MENU] + [+] + [CHANGE DATA] keys down while
simultaneously reconnecting the mains voltage.
Release the keys; the frequency converter has now
been programmed for the factory setting.
MG.28.H2.02 -
10