EasyManuals Logo
Home>Danfoss>DC Drives>AKD 2800

Danfoss AKD 2800 User Manual

Danfoss AKD 2800
77 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #69 background imageLoading...
Page #69 background image
AKD 2800
All about AKD
2800
Technical data, mains supply 1 x 220 - 240 V/3 x 200-240 V
According to . international
standards
Type 2
22
28
88
80
00
03
33
32
22
28
88
80
00
05
55
52
22
28
88
80
00
07
77
72
22
28
88
81
11
11
11
12
22
28
88
81
11
15
55
52
22
28
88
82
22
22
22
22
22
28
88
84
44
40
00
0
Output current I
INV.
[A] 2.2 3.2 4.2 6.0 6.8 9.6 16
(3 x 200-240V) I
MAX
(60s) [A] 3.5 5.1 6.7 9.6 10.8 15.3 25.6
Output power (230 V) S
INV.
[KVA] 0.9 1.3 1.7 2.4 2.7 3.8 6.4
Typical shaft output P
M,N
[kW] 0.37 0.55 0.75 1.1 1.5 2.2 3.7
Typical shaft output P
M,N
[HP] 0.5 0.75 1.0 1.5 2.0 3.0 5.0
Max. cable cross
section, motor
[mm
2
/AWG]
1)
4/10 4/10 4/10 4/10 4/10 4/10 4/10
Input current I
L,N
[A] 5.9 8.3 10.6 14.5 15.2 - -
(1 x 220-240 V) I
L,MAX
(60s) [A] 9.4 13.3 16.7 23.2 24.3 - -
Input current I
L,N
[A] 2.9 4.0 5.1 7.0 7.6 8.8 14.7
(3 x 200-240 V) I
L,MAX
(60s) [A] 4.6 6.4 8.2 11.2 12.2 14.1 23.5
Max. cable cross
section, power
[mm
2
/AWG]
1)
4/10 4/10 4/10 4/10 4/10 4/10 4/10
Max. pre-fuses [A]/UL
2)
[A] 20/20 20/20 20/20 20/20 20/20 20/20 25/25
Efficiency
3)
[%]95959595959595
Power loss at 100%
load
[W]2435486994125231
Weight [kg] 2.0 2.0 2.0 2.0 2.0 3,7 6.0
Enclosure
4
type IP 20 IP 20 IP 20 IP 20 IP 20 IP 20 IP 20
1. American Wire Gauge. Max. cable cross
section is the largest cable cross section that can
be attached to the terminals. Always observe
national and local regulations.
2. Type gG pre-fuses must be used. If you want
to maintain UL/cUL you must use pre-fuses of the
type Bussmann KTN-R 200 V, KTS-R 500 V o
r
FerrazShawmut,typeATMR(max.30A).Thefuses
must be placed for protection in a circuit that is
capable of supplying a maximum of 1
00,000 amps
RMS (symmetrical), 500 V maximum.
3. Measured using a 25 m screened/armoured motor
cable with a rated load and rated f
requency.
4. IP20 is standard for AKD 2805-2875,
whereas NEMA 1 is an option.
MG.28.H2.02 -
69

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss AKD 2800 and is the answer not in the manual?

Danfoss AKD 2800 Specifications

General IconGeneral
BrandDanfoss
ModelAKD 2800
CategoryDC Drives
LanguageEnglish

Related product manuals