point that the control regulates against is lowered or raised respectively.
When you increase the CURVE value, the heat curve will become steeper
and when you reduce it, it will become flatter.
This is the most energy and cost efficient way to set the indoor tempera-
ture and should therefore be used for long term temperature settings.
1. Supply temperature (°C)
2.
Maximum setpoint value
3. Outdoor temperature (°C)
4. 0°C
5. Set value (standard 40°C)
The following parameters can be adjusted in the HEATING menu:
Parameter Description
CURVE If the CURVE value is increased, the heat curve will become
steeper and if the value is reduced, it will become flatter. Raise
or lower as necessary to obtain as even an indoor temperature
as possible.
MIN Lowest set point for supply temperature.
MAX Highest set point for supply temperature.
CURVE 5 Used to adjust the heat curve at an outdoor temperature of
+5°C.
CURVE 0 Used to adjust the heat curve at an outdoor temperature of 0°C
CURVE -5 Used to adjust the heat curve at an outdoor temperature of
-5°C.
18 – User manual VUGFB102