5.3Tanktemperature
ParametersindicatedwithanIDno.like"1x607"meanauniversal
parameter.
xstandsforcircuit/parametergroup.
MENU>Settings>Tanktemperature
Chargedifference
1x193
SetthenumberofdegreesabovethedesiredDHWtemperaturethatwill
resultintheDHWheating(charging)temperature.
SeeAppendix“ParameterIDoverview
Value:
NumberofdegreestobeaddedtothedesiredDHW
temperaturetoobtaintheDHWheating(charging)
temperature.
X
=
Time
#1#
=
Chargingdifference(ID1x193)
#2#
=
DesiredDHWtemperature
#3#
=
Startdifference(ID1x195)
#4#
=
ActualDHWtemperature
#5#
=
DHWheating/chargingactivity
ThedesiredDHWtemperatureisrelatedtothetanktemperature
sensor.
Iftwotanktemperaturesensorsareinstalled,therelationistothe
uppertanktemperaturesensor.
VI.GU.L2.02
©Danfoss|2017.09|109