EKC 202D / EKC 302D Instructions RI8KX753 © Danfoss 09/2016 5
Setting:
1 Open parameter r12 and stop the
regulation
2 Select electric connection based on
the drawings on page 2
3 Open parameter o61 and set the elec-
tric connection number in it
4 Open parameter r12 and start the
regulation
5 Go through the survey of factory set-
tings. Make any necessary changes in
the respective parameters.
6 For network. Set the address in o03
and start scanfunction in the system
manager.
English
Parameters
EL-diagram
number
(page 2)
Min.-
value
Max.-
value
Factory
setting
Actual
setting
Function Codes 1 2 3
Normal operation
Temperature (set point) --- -50.0°C 50.0°C 2.0°C
Thermostat
Dierential *** r01 0.0 K 20.0K 2.0 K
Max. limitation of setpoint setting *** r02 -49.0°C 50°C 50.0°C
Min. limitation of setpoint setting *** r03 -50.0°C 49.0°C -50.0°C
Adjustment of temperature indication r04 -20.0 K 20.0 K 0.0 K
Temperature unit (°C/°F) r05 °C °F °C
Correction of the signal from S4 r09 -10.0 K +10.0 K 0.0 K
Correction of the signal from S3 r10 -10.0 K +10.0 K 0.0 K
Manual service, stop regulation, start regulation (-1,
0, 1)
r12 -1 1 0
Displacement of reference during night operation r13 -10.0 K 10.0 K 0.0 K
Denition and weighting, if applicable, of thermostat
sensors - S4% (100%=S4, 0%=S3)
r15 0% 100% 100%
Activation of reference displacement r40 r39 OFF ON OFF
Value of reference displacement (activate via r39 or DI) r40 -50.0 K 50.0 K 0.0 K
Alarm
Delay for temperature alarm A03 0 min 240 min 30 min
Delay for door alarm *** A04 0 min 240 min 60 min
Delay for temperature alarm after defrost A12 0 min 240 min 90 min
High alarm limit *** A13 -50.0°C 50.0°C 8.0°C
Low alarm limit *** A14 -50.0°C 50.0°C -30.0°C
Alarm delay DI1 A27 0 min 240 min 30 min
Alarm delay DI2 A28 0 min 240 min 30 min
Signal for alarm thermostat. S4% (100%=S4, 0%=S3) A36 0% 100% 100%
Compressor
Min. ON-time c01 0 min 30 min 0 min
Min. OFF-time c02 0 min 30 min 0 min
Compressor relay 1 must cutin and out inversely
(NC-function)
c30 0
OFF
1
ON
0
OFF
External relays (zero-crossing control – only EKC 302D)
Must be 'ON' when connecting to external relays
c70 OFF ON ON
Defrost
Defrost method (none/EL/GAS/BRINE) d01 no bri EL
Defrost stop temperature d02 0.0°C 25.0°C 6.0°C
Interval between defrost starts d03 0 hours 48 hours 8 hours
Max. defrost duration d04 0 min 180 min 45 min
Displacement of time on cutin of defrost at start-up d05 0 min 240 min 0 min
Drip o time d06 0 min 60 min 0 min
Delay for fan start after defrost d07 0 min 60 min 0 min
Fan start temperature d08 -15.0°C 0.0°C -5.0°C
Fan cutin during defrost
0: Stopped
1: Running
2: Running during pump down and defrost
d09 0 2 1
Defrost sensor (0=time, 1=S5, 2=S4) d10 0 2 0
Pump down delay d16 0 min 60 min 0 min
Max. aggregate refrigeration time between two
defrosts
d18 0 hours 48 hours 0 hours
Defrost on demand - S5 temperatures permitted vari-
ation during frost build-up. On central plant choose
20 K (=o)
d19 0.0 K 20.0 k 20.0 K
Fan
Fan stop at cutout compressor F01 no yes no
Delay of fan stop F02 0 min 30 min 0 min
Fan stop temperature (S5) F04 -50.0°C 50.0°C 50.0°C
Real time clock
Six start times for defrost.
Setting of hours.
0=OFF
t01-
t06
0 hours 23 hours 0 hours
Six start times for defrost.
Setting of minutes.
0=OFF
t11-
t16
0 min 59 min 0 min
Clock - Setting of hours *** t07 0 hours 23 hours 0 hours
Clock - Setting of minute *** t08 0 min 59 min 0 min
Clock - Setting of date *** t45 1 31 1
Clock - Setting of month *** t46 1 12 1
Clock - Setting of year *** t47 0 99 0
Miscellaneous
Delay of output signals after start-up o01 0 s 600 s 5 s
Input signal on DI1. Function:
0=not used. 1=status on DI1. 2=door function with
alarm when open. 3=door alarm when open. 4=defrost
start (pulse-signal). 5=ext.main switch. 6=night
operation 7=change reference (activate r40). 8=alarm
function when closed. 9=alarm function when open.
10=case cleaning (pulse signal). 11=forced cooling.
12=not used. 13=case shut down (302D).
o02 1 13 0
Network address (0= o) o03 0 240 0
On/O switch (Service Pin message)
IMPORTANT! o61 must be set prior to o04
o04 OFF ON OFF
EKC 202D: SW = 2.2x
EKC 302D: SW = 1.2x