2 Instructions RI8GT752 © Danfoss 02/2010 EKC 315A
!! U
77-78
: 24 V +/-10% !!
Kabel fx, Cable ex., Kabel z.B., câble fx
L < 25 m : 0.75 mm
2
25 m < L < 75 m : 1.5 mm
2
75 m < L : 2.5 mm
2
DANSK ENGLISH
Tilslutninger
Connections
Data kommunikation
Data communication
Datenkommunikation
Communication des données
Nødvendige tilslutninger
Klemme:
25-26 Forsyningsspænding 24 V a.c.
17-18 Kun ved TQ aktuator: Signal fra aktuator
20-21 Pt 1000 føler ved fordamperafgang (S2)
14-15 Tryktransmitter type AKS 33
9-10 Relækontakt til start/stop af magnetventil
1-2 Kontaktfunktion til start/stop af reguleringen. Hvis der
ikke tilsluttes en kontakt, skal klemme 1 og 2 kortsluttes.
Applicationbestemte tilslutninger
Klemme:
21-22 Pt 1000 føler til måling af lufttemperatur (S3)
12-13 Alarmrelæet
Der er forbindelse imellem 12 og 13 i alarmsituationer, og
når regulatoren er spændingsløs
18-19 Strømsignal fra anden regulering (Ext.Ref.)
23-24 Spænding til aktuator AKV/TQ
2-5 Strømudgang til visning af overhedning eller lufttemper-
atur. Eller til signal til et slavemodul. Eller styring af ICM
ventil.
3-4 Datakommunikation
Monteres kun, hvis der også er monteret et datakommu-
nikationsmodul.
Det er vigtigt, at installationen af datakommunikationsk-
ablet udføres korrekt.
Se separat litteratur nr. RC8AC...
Necessary connections
Terminals:
25-26 Supply voltage 24 V a.c.
17-18 Only at TQ actuator: Signal from actuator
20-21 Pt 1000 sensor at evaporator outlet (S2)
14-15 Pressure transmitter type AKS 33
9-10 Relay switch for start/stop of solenoid valve
1-2 Switch function for start/stop of regulation. If a switch
is not connected, terminals 1 and 2 must be
shortcircuited.
Application dependent connections
Terminal:
21-22 Pt 1000 sensor for measuring air temperature (S3)
12-13 Alarm relay
There is connection between 12 and 13 in alarm
situa tions and when the controller is dead
18-19 Current signal from other regulation (Ext.Ref.)
23-24 Supply to actuator AKV/TQ
2-5 Current output for showing superheat or air tempera-
ture. Or for signal to a slave module. Or control of ICM
valve.
3-4 Data communication
Mount only, if a data communication module has been
mounted.
It is important that the installation of the data communica-
tion cable be done correctly.
Cf. separate literature No. RC8AC...
ICAD skal forsynes fra ek-
stern kilde med 24 V d.c.
ICAD must be supplied
with 24 V DC from an
external source.
Das ICAD muss von einer
externen Quelle mit 24
V Gleichstrom versorgt
werden.
ICAD doit être alimenté
par une source externe de
24 V c.c.

Other manuals for Danfoss EKC 315A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss EKC 315A and is the answer not in the manual?

Danfoss EKC 315A Specifications

General IconGeneral
BrandDanfoss
ModelEKC 315A
CategoryController
LanguageEnglish

Related product manuals