EasyManuals Logo
Home>Danfoss>Controller>ERC 214

Danfoss ERC 214 User Manual

Danfoss ERC 214
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #22 background imageLoading...
Page #22 background image
22
FR · ERC 21X user manual · DKRCC.ES.RL0.H3.02/520H9656 · ©Danfoss
7| Parameter table
7.1| Parameter table - ERC 211
Parameter name - ERC 211 Code Min Max Unit
App. 0
(Def.)
App. 1 App. 2 App. 3 App. 4 App. 5
Conguration cFg
Main switch
-1=service, 0=OFF, 1=ON
r12 -1 1 1 1 1 1 1 1
Predened applications
AP0, AP1, AP2, AP3, AP4, AP5
o61 AP0 AP5 AP0 AP1 AP2 AP3 AP4 AP5
Sensor type selection
n5=NTC 5 K, n10=NTC 10 K,
Ptc=PTC, Pt1=Pt1000
o06 n5 Pt1 n10 n10 n10 n10 n10 n10
Reference/thermostat r--
Temperature setpoint r00 -100.0 200.0 C/F 2.0 8.0 4.0 4.0 40.0 2.0
Dierential r01 0.1 20.0 K 2.0 2.0 2.0 2.0 2.0 2.0
Min set point limitation r02 -100.0 200.0 C/F -35.0 4.0 2.0 2.0 20.0 -35.0
Max set point limitation r03 -100.0 200.0 C/F 50.0 20.0 6.0 6.0 60.0 50.0
Display oset
(correction value in display
temperature)
r04 -10.0 10.0 K 0.0 0.0 0.0 0.0 0.0 0.0
Display unit (°C/°F) r05 -C -F -C -C -C -C -C -C
Calibration of Sair
(offset for air temperature
calibration)
r09 -20.0 20.0 K 0.0 0.0 0.0 0.0 0.0 -
Main switch
-1=service, 0=OFF, 1=ON
r12 -1 1 1 1 1 1 1 -
Night set back
(offset temperature during night
mode)
r13 -50.0 50.0 K 0.0 0.0 0.0 0.0 0.0 0.0
Thermostat reference
displacement
(offset temperature)
r40 -50.0 50.0 K 0.0 0.0 0.0 0.0 0.0 -
Pull-down duration r96 0 960 min 0 - 0 0 - -
Pull-down limit temperature r97 -100.0 200.0 C/F 0.0 - 0.0 0.0 - -
Alarm A--
Delay for temperature alarm
during normal conditions
A03 0 240 min 30 45 45 45 30 30
Delay for temperature alarm
during pull-down/start-up/
defrost
A12 0 240 min 60 60 90 90 60 60
High temperature alarm limit
(Cabinet/room)
A13 -100.0 200.0 C/F 8.0 16 10 10 80 8.0
Low temperature alarm limit A14 -100.0 200.0 C/F -30.0 0.0 0.0 0.0 10 -30.0
DI1 delay
(time delay for selected DI1
function)
A27 0 240 min 30 30 30 30 30 30
Condenser high alarm limit
A37 0 200 C/F 80 80 80 80 - -
Condenser high block limit A54 0 200 C/F 85 85 85 85 - -
Voltage protection enable
A72 no yES no no no no no no
Minimum cut-in voltage A73 0 270 V 0 0 0 0 0 0
Minimum cut-out voltage A74 0 270 V 0 0 0 0 0 0
Note: hidden parameters are greyed out

Other manuals for Danfoss ERC 214

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss ERC 214 and is the answer not in the manual?

Danfoss ERC 214 Specifications

General IconGeneral
BrandDanfoss
ModelERC 214
CategoryController
LanguageEnglish

Related product manuals