Parameter name - ERC 214 Code Min Max Unit
App. 0
(Def.)
App. 1 App. 2 App. 3 App. 4 App. 5 App. 6
Defrost d--
Defrost method
no=no defrost, nAt=natural,
EL=electrical, gAS=hot gas
d01 no gAS EL nAt EL EL EL EL EL
Defrost stop temperature d02 0.0 50.0 C/F 6.0 - - - 6.0 6.0 6.0
Defrost interval d03 0 240 hours 8 6 8 12 8 12 8
Max defrost time d04 0 480 min 30 45 15 15 30 30 30
Defrost delay at power up
(or DI signal)
d05 0 240.0 min 0 0 0 0 0 0 -
Drip delay d06 0 60 min 0 0 0 0 0 0 5
Fan delay after defrost d07 0 60 min 0 0 0 0 0 0 5
Fan start temperature
after defrost
d08 -50.0 0.0 C/F -5.0 - - - -5.0 -5.0 -
Fan during defrost d09 oFF on on on on on on on on
Defrost stop sensor
configuration non=time,
Air=Sair (air temperature),
dEF=S5 (defrost sensor)
d10 non dEF non non non non dEF dEF non
Compressor accumulated
runtime to start defrost
0=OFF
d18 0 96 hours 0 0 0 0 0 0 -
Defrost on demand
20.0=OFF
d19 0.0 20.0 K 20.0 - - - 20.0 20.0 -
Defrost delay after pull-down
0=OFF
d30 0 960 min 0 0 0 0 0 0 -
Fan control F--
Fan at compressor cutout
FFc=fan follow compressor,
FAo=fan always ON,
FPL= fan pulsating
F01 FFc FPL FAo FAo FAo FAo FAo FAo FAo
Fan stop evaporator
temperature
50.0=OFF
F04 -50.0 50.0 C/F 50.0 - - - 50.0 50.0 -
Fan ON cycle F07 0 15 min 2 2 2 2 2 2 2
Fan OFF cycle F08 0 15.0 min 2 2 2 2 2 2 2
Compressor c--
Compressor minimum ON time C01 0 30 min 0 0 0 0 0 0 0
Compressor minimum OFF time C02 0 30 min 2 2 2 2 2 2 2
Compressor OFF delay
at door open
C04 0 15 min 0 0 0 0 0 0 1
Zero crossing selection C70 no yES yES yES yES yES yES yES yES
Note: hidden parameters are greyed out