EasyManuals Logo
Home>Danfoss>Media Converter>MCA 121

Danfoss MCA 121 User Manual

Danfoss MCA 121
59 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #30 background imageLoading...
Page #30 background image
8-05 End-of-Timeout Function
Option: Function:
until 8-06 Reset Control Timeout toggles. Then
the frequency converter resumes its original
set-up.
[1] * Resume set-
up
Resumes the set-up active prior to the time-
out.
8-06 Reset Control Word Timeout
This parameter is active only when Hold set-up [0] has been
selected in 8-05 End-of-Timeout Function.
Option: Function:
[0] * Do not reset
Retains the set-up specified in 8-04 Control
Word Timeout Function, following a control
word time-out.
[1] Do reset Returns the frequency converter to the
original set-up following a control word time-
out. The frequency converter performs the
reset and then immediately reverts to the Do
not reset [0] setting
8-10 Control Word Profile
Select the interpretation of the control and status words
corresponding to the installed fieldbus. Only the selections valid
for the fieldbus installed in slot A will be visible in the LCP
display.
For guidelines in selection of FC profile [0] and PROFIdrive profile
[1] please refer to the Serial communication via RS 485 Interface
section.
For additional guidelines in the selection of PROFIdrive profile [1],
ODVA [5] and CANopen DSP 402 [7], please refer to the Operating
Instructions for the installed fieldbus.
Option: Function:
[0] * FC profile
[1] PROFIdrive profile
[5] ODVA
[7] CANopen DSP 402
[8] MCO
8-13 Configurable Status Word STW
Option: Function:
This parameter enables configuration of
bits 12 15 in the status word.
[0] No function
[1] * Profile Default Function corresponds to the profile
default selected in 8-10 Control Profile.
[2] Alarm 68 Only Only set in case of an Alarm 68.
[3] Trip excl Alarm
68
Set in case of a trip, except if the trip is
executed by an Alarm 68.
[10] T18 DI status. The bit indicates the status of terminal
18
*1
.
[11] T19 DI status. The bit indicates the status of terminal
19
*1
.
8-13 Configurable Status Word STW
Option: Function:
[12] T27 DI status. The bit indicates the status of terminal
27
*1
.
[13] T29 DI status. The bit indicates the status of terminal
29
*1
.
[14] T32 DI status. The bit indicates the status of terminal
32
*1
.
[15] T33 DI status. The bit indicates the status of terminal
33
*1
.
[16] T37 DI status The bit indicates the status of terminal
37
*2
.
[21] Thermal
warning
The thermal warning turns on when the
temperature exceeds the limit in the
motor, the frequency converter, the brake
resistor, or the thermistor..
[30] Brake fault
(IGBT)
Output is Logic ‘1’ when the brake IGBT is
short-circuited. Use this function to
protect the frequency converter if there is
a fault on the brake modules. Use the
output/relay to cut out the main voltage
from the frequency converter.
[40] Out of ref
range
[60] Comparator 0 See par. group 13-1*. If Comparator 0 is
evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[61] Comparator 1 See par. group 13-1*. If Comparator 1 is
evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[62] Comparator 2 See par. group 13-1*. If Comparator 2 is
evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[63] Comparator 3 See par. group 13-1*. If Comparator 3 is
evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[64] Comparator 4 See par. group 13-1*. If Comparator 4 is
evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[65] Comparator 5 See par. group 13-1*. If Comparator 5 is
evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[70] Logic Rule 0 See par. group 13-4*. If Logic Rule 0 is
evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[71] Logic Rule 1 See par. group 13-4*. If Logic Rule 1 is
evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[72] Logic Rule 2 See par. group 13-4*. If Logic Rule 2 is
evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[73] Logic Rule 3 See par. group 13-4*. If Logic Rule 3 is
evaluated as TRUE, the output will go
high. Otherwise, it will be low.
Parameters MCA 121 EtherNet/IP
MG.90.J3.02 - VLT
®
is a registered Danfoss trademark 29
6
6

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss MCA 121 and is the answer not in the manual?

Danfoss MCA 121 Specifications

General IconGeneral
BrandDanfoss
ModelMCA 121
CategoryMedia Converter
LanguageEnglish

Related product manuals