12-06 Name Servers
Range: Function:
0* [0 - 2147483647 ] IP addresses of Domain Name Servers.
Can be automatically assigned when
using DHCP.
12-07 Domain Name
Range: Function:
0 [0 - 2147483647 ] Domain name of the attached network.
Can be automatically assigned when
using DHCP.
12-08 Host Name
Range: Function:
Blank [0-19 characters] Logical (given) name of option.
12-09 Physical Address
Range: Function:
0* [0 - 0 ] Read only Displays the Physical (MAC) address of
the option.
6.2.2 12-1* Ethernet Link Parameters
12-1* Ethernet Link parameters
Option: Function:
Applies for whole parameter group.
[0] Port 1
[1] Port 2
12-10 Link Status
Option: Function:
12-11 Link Duration
Range: Function:
Application dependent* [Application dependant]
12-12 Auto Negotiation
Option: Function:
Configures Auto Negotiation of Ethernet link
parameters, for each port: ON or OFF.
[0] Off
Link Speed and Link Duplex can be configured in
12-13 Link Speed and 12-14 Link Duplex.
[1] On
12-13 Link Speed
Option: Function:
Forces the link speed for each port in 10 or 100
Mbps. If 12-12 Auto Negotiation is set to: ON,
this parameter is read only and displays the
actual link speed. “None” is displayed if no link
is present.
[0] * None
[1] 10 Mbps
[2] 100 Mbps
12-14 Link Duplex
Option: Function:
Forces the duplex for each port to Full or Half
duplex. If 12-12 Auto Negotiation is set to: ON,
this parameter is read only.
[0] Half Duplex
[1] * Full Duplex
6.2.3 12-2* Process Data
12-20 Control Instance
Range: Function:
[None, 20, 21, 100,
101, 103]
Read only. Displays the originator-to-
target connection point. If no CIP
connection is present “None” is
displayed.
12-21 Process Data Config Write
Range: Function:
[[0 - 9] PCD read 0 - 9] Configuration of readable process
data.
NOTE
For configuration of 2-word (32-bit) parameter read/write,
use 2 consecutive arrays in 12-21 Process Data Config Write
and 12-22 Process Data Config Read.
12-22 Process Data Config Read
Range: Function:
[[0 - 9] PCD read 0 - 9] Configuration of readable process
data.
12-28 Store Data Values
Option: Function:
This parameter activates a function that stores
all parameter values in the non-volatile
memory (EEPROM) thus retaining parameter
values at power-down.
The parameter returns to “Off”.
[0] * Off The store function is inactive.
[1] Store All
set-ups
All parameter value will be stored in the non-
volatile memory, in all four setups.
12-29 Store Always
Option: Function:
Activates function that will always store received
parameter data in non-volatile memory (EEPROM).
[0] * Off
[1] On
Parameters MCA 121 EtherNet/IP
32 MG.90.J3.02 - VLT
®
is a registered Danfoss trademark
6
6

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss MCA 121 and is the answer not in the manual?

Danfoss MCA 121 Specifications

General IconGeneral
BrandDanfoss
ModelMCA 121
CategoryMedia Converter
LanguageEnglish